FIR17-00337
| INSP-Final Inspection | 8/28/2017 | 8/28/2017 | 8/28/2017 2:39:29 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
|
FIR17-00337
| INSP-Sprinkler Rough-in | 8/28/2017 | 8/28/2017 | 8/28/2017 2:39:04 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in area of work complete, area of work approved for cover.
|
FIR16-00606
| INSP-Sprinkler Rough-in/Hydro | 8/28/2017 | 8/28/2017 | 8/28/2017 2:38:14 PM | P | PART |
|
|
Hydrostatic test complete for parking level dry system, levels 2, 4 and 5 wet systems. Level 3 had a visable leak, leak was repaired, system will be rechecked on 29AUG2017
|
BLD17-02276
| FIRE-Final Inspection | 8/25/2017 | 8/28/2017 | 8/28/2017 10:52:20 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
BLD17-01409
| FIRE-Final Inspection | 8/24/2017 | 8/28/2017 | 8/28/2017 10:34:18 AM | A | PASS |
|
|
Fire sprinkler inspection complete (fire sprinkler permit for this space not attached in project related cases FIR17-00401), no fire alarm modification, fire extinguisher will be mounted in discussed location. Final life fire safety inspection passed/complete.
|
FIR17-00401
| INSP-Final Inspection | 8/28/2017 | 8/28/2017 | 8/28/2017 10:32:47 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
BLD17-01060
| FIRE-Final Inspection | 8/24/2017 | 8/28/2017 | 8/28/2017 10:10:26 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher in common area with current inspection tag. Final life fire safety inspection passed/complete.
|
FIR17-00030
| INSP-Sprinkler Rough-in/Hydro | 8/25/2017 | 8/28/2017 | 8/28/2017 9:54:36 AM | A | PASS |
|
|
Hydrostatic test for overhead fire sprinkler piping complete. Rough to cover inspection for overhead fire sprinkler piping coplete, approved for cover. Insulation is going to be spray foam type to the bottom of the roof deck, tenting not required. If spray foam comes in contact with CPVC then documentation will be required to verify compatibility of spray foam with CPVC piping.
|
FIR17-00001
| INSP-Final Inspection | 8/27/2017 | 8/28/2017 | 8/28/2017 9:04:32 AM | A | PART |
|
|
Partial final inspection for fire sprinklers complete, permit can be finaled when alarm inspection is complete for associated fire alarm components.
|
FIR17-00217
| INSP-Sprinkler Rough-in/Hydro | 8/27/2017 | 8/28/2017 | 8/28/2017 9:03:02 AM | A | PASS |
|
|
Rough to cover inspection for level 1 complete, approved for cover.
|
FIR17-00337
| INSP-Final Inspection | 8/28/2017 | 8/28/2017 | 8/28/2017 8:36:29 AM | P | CANC |
|
|
Mike Martin is the contact for this rough in inspection. According to Mike this inspection has already been done. Just needed to be logged in. Thank you for all your help. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|