Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00337 INSP-Final Inspection8/28/20178/28/20178/28/2017 2:39:29 PMPPASS
Final fire sprinkler inspection for area of work complete.
FIR17-00337 INSP-Sprinkler Rough-in8/28/20178/28/20178/28/2017 2:39:04 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping/pendant heads in area of work complete, area of work approved for cover.
FIR16-00606 INSP-Sprinkler Rough-in/Hydro8/28/20178/28/20178/28/2017 2:38:14 PMPPART
Hydrostatic test complete for parking level dry system, levels 2, 4 and 5 wet systems. Level 3 had a visable leak, leak was repaired, system will be rechecked on 29AUG2017
BLD17-02276 FIRE-Final Inspection8/25/20178/28/20178/28/2017 10:52:20 AMAPASS
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
BLD17-01409 FIRE-Final Inspection8/24/20178/28/20178/28/2017 10:34:18 AMAPASS
Fire sprinkler inspection complete (fire sprinkler permit for this space not attached in project related cases FIR17-00401), no fire alarm modification, fire extinguisher will be mounted in discussed location. Final life fire safety inspection passed/complete.
FIR17-00401 INSP-Final Inspection8/28/20178/28/20178/28/2017 10:32:47 AMAPASS
Final fire sprinkler inspection passed/complete
BLD17-01060 FIRE-Final Inspection8/24/20178/28/20178/28/2017 10:10:26 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher in common area with current inspection tag. Final life fire safety inspection passed/complete.
FIR17-00030 INSP-Sprinkler Rough-in/Hydro8/25/20178/28/20178/28/2017 9:54:36 AMAPASS
Hydrostatic test for overhead fire sprinkler piping complete. Rough to cover inspection for overhead fire sprinkler piping coplete, approved for cover. Insulation is going to be spray foam type to the bottom of the roof deck, tenting not required. If spray foam comes in contact with CPVC then documentation will be required to verify compatibility of spray foam with CPVC piping.
FIR17-00001 INSP-Final Inspection8/27/20178/28/20178/28/2017 9:04:32 AMAPART
Partial final inspection for fire sprinklers complete, permit can be finaled when alarm inspection is complete for associated fire alarm components.
FIR17-00217 INSP-Sprinkler Rough-in/Hydro8/27/20178/28/20178/28/2017 9:03:02 AMAPASS
Rough to cover inspection for level 1 complete, approved for cover.
FIR17-00337 INSP-Final Inspection8/28/20178/28/20178/28/2017 8:36:29 AMPCANC
Mike Martin is the contact for this rough in inspection. According to Mike this inspection has already been done. Just needed to be logged in. Thank you for all your help. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus