ELE18-02366
| Final | 8/27/2018 | 8/28/2018 | 8/28/2018 2:52:02 PM | P | NR |
|
|
Please call Brian, the electrical foreman when you are on your way ###-#### Phone #: ###-#### Inspection requested via web by Ashley White Not ready rescheduled for Wed Morning.
|
ELE18-02296
| Final | 8/28/2018 | 8/28/2018 | 8/28/2018 2:16:47 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 110.26- Electrical rooms shall not be used as storage rooms. Minimum work space shall be provided. 210.71- Meeting rooms 215 and larger shall have a floor receptacle installed a minimum of 6' from all walls.
|
ELE18-03275
| Final | 8/27/2018 | 8/28/2018 | 8/28/2018 1:21:05 PM | P | PASS |
|
|
Check in with receptionist, she knows where the dryers are installed. Phone #: ###-#### Inspection requested via web by sam petterson Final ok
|
ELE18-03275
| Electrical Rough-In | 8/28/2018 | 8/28/2018 | 8/28/2018 1:20:54 PM | P | PASS |
|
|
Check in with receptionist, she knows where the dryers are installed. Phone #: ###-#### Inspection requested via web by sam petterson Rough in ok.
|
ELE18-03141
| Electrical Rough-In | 8/27/2018 | 8/28/2018 | 8/28/2018 11:29:03 AM | A | PART |
|
|
partial rough- in in basement Phone #: ###-#### Inspection requested via web by Winters LLC Basement living room and bathroom only rough in ok cover
|
ELE18-02186
| Final | 8/27/2018 | 8/28/2018 | 8/28/2018 11:05:25 AM | A | PASS |
|
|
This permit is for the basement only Phone #: ###-#### Inspection requested via web by Eric Schroeder Final ok
|
ELE18-02366
| Electrical Rough-In | 8/27/2018 | 8/28/2018 | 8/28/2018 10:41:57 AM | A | PASS |
|
|
Please call Brian, the electrical foreman when you are on your way ###-#### Phone #: ###-#### Inspection requested via web by Ashley White Correct # for Brian ###-####. Listings confirmed. rough in ok
|
ELE18-03062
| Rough-In Permanent Service | 8/27/2018 | 8/28/2018 | 8/28/2018 10:16:28 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn 110.3- Recessed can junction box covers shall be installed as per instructions. Covers shall be tight to boxes. Kitchen and over stair landing. 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage. Kitchen island, 2 in garage, front rm, 3 level 2 hall. 300-14- Minimum of 6" of free conductor shall be present at each outlet. 2 receptacles in front room no free conductor on equipment grounds
|