Inspections for the day of: Tuesday, August 28, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-02366 Final8/27/20188/28/20188/28/2018 2:52:02 PMPNR
Please call Brian, the electrical foreman when you are on your way ###-#### Phone #: ###-#### Inspection requested via web by Ashley White
Not ready rescheduled for Wed Morning.
ELE18-02296 Final8/28/20188/28/20188/28/2018 2:16:47 PMPFAIL
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
110.26- Electrical rooms shall not be used as storage rooms. Minimum work space shall be provided.
210.71- Meeting rooms 215 and larger shall have a floor receptacle installed a minimum of 6' from all walls.
ELE18-03275 Final8/27/20188/28/20188/28/2018 1:21:05 PMPPASS
Check in with receptionist, she knows where the dryers are installed. Phone #: ###-#### Inspection requested via web by sam petterson Final ok
ELE18-03275 Electrical Rough-In8/28/20188/28/20188/28/2018 1:20:54 PMPPASS
Check in with receptionist, she knows where the dryers are installed. Phone #: ###-#### Inspection requested via web by sam petterson Rough in ok.
ELE18-03141 Electrical Rough-In8/27/20188/28/20188/28/2018 11:29:03 AMAPART
partial rough- in in basement Phone #: ###-#### Inspection requested via web by Winters LLC
Basement living room and bathroom only rough in ok cover
ELE18-02186 Final8/27/20188/28/20188/28/2018 11:05:25 AMAPASS
This permit is for the basement only Phone #: ###-#### Inspection requested via web by Eric Schroeder Final ok
ELE18-02366 Electrical Rough-In8/27/20188/28/20188/28/2018 10:41:57 AMAPASS
Please call Brian, the electrical foreman when you are on your way ###-#### Phone #: ###-#### Inspection requested via web by Ashley White
Correct # for Brian ###-####.
Listings confirmed. rough in ok
ELE18-03062 Rough-In Permanent Service8/27/20188/28/20188/28/2018 10:16:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by Bob Glenn
110.3- Recessed can junction box covers shall be installed as per instructions. Covers shall be tight to boxes. Kitchen and over stair landing.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage. Kitchen island, 2 in garage, front rm, 3 level 2 hall.
300-14- Minimum of 6" of free conductor shall be present at each outlet. 2 receptacles in front room no free conductor on equipment grounds