ELE13-01749
| ELE-Aging Inspection | 8/28/2018 | 8/28/2018 | 8/31/2018 3:29:23 PM | | DONE |
|
|
DOC expired permit
|
ELE13-01899
| ELE-Aging Inspection | 8/28/2018 | 8/28/2018 | 8/31/2018 3:26:58 PM | | DONE |
|
|
contractor been notified
|
ELE18-01034
| Final | 8/28/2018 | 8/28/2018 | 8/28/2018 3:26:11 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall...ok to final
|
ELE18-03273
| Final | 8/27/2018 | 8/28/2018 | 8/28/2018 2:52:46 PM | P | NR |
|
|
Late afternoon if possible Phone #: ###-#### Inspection requested via web by Same Electric...windows within 5ft of tub waterline shall be tempered, light within 5ft of tub shall be nonmettalic and GFCI protected, metal gazebo shall be bonded to hot tub, and load calculation on 100A panel is required to approve addition of 40A hot tub breaker on bussing
|
ELE18-03273
| Electrical Rough-In | 8/28/2018 | 8/28/2018 | 8/28/2018 2:47:18 PM | P | PASS |
|
|
Late afternoon if possible Phone #: ###-#### Inspection requested via web by Same Electric...8/3 romex thru attic for 40A hot tub circuit...GFCI protected disconnect...pvc ran to tub...underground correct depth ok to cover
|
ELE18-02703
| Final | 8/28/2018 | 8/28/2018 | 8/28/2018 2:13:46 PM | P | PEND |
|
|
Early as possible please -Crew needs to be off site by 10:00 am. Phone #: ###-#### Inspection requested via web by Laurie Hoelscher...contractor rep Drew ###-#### stated job complete...pillar lights being installed by others...others will need to pull permit for work..will final permit once verified permit pulled by others
|
ELE18-01686
| Electrical Rough-In | 8/27/2018 | 8/28/2018 | 8/28/2018 1:44:41 PM | P | PASS |
|
|
Ceiling cover. Von is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen... northside complete ceiling grid and remaining southside ceiling grid...Lobby is only area left-ceilings undecided
|
ELE18-03281
| Electrical Rough-In | 8/27/2018 | 8/28/2018 | 8/28/2018 1:12:03 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dustin Kuester...ok to cover walls and ceiling fished in or using existing lighting
|
ELE18-03000
| Electrical Rough-In | 8/28/2018 | 8/28/2018 | 8/28/2018 12:55:24 PM | P | PASS |
|
|
Pls contact Brad (Foreman) @ ###-#### or Preston (Electrician) @ ###-#### one hr prior or if you have any questions. Thank you. Inspection requested via web by Rob Maes...
UL listed equipment...rough-start of solar install...discussed install, feeds thru attic of shed, pipe to house from shed existing, bonding and grounding so far
|
ELE18-03287
| Final | 8/28/2018 | 8/28/2018 | 8/28/2018 12:18:44 PM | P | PASS |
|
|
Call homeowner when on the way please ###-####
Ground works inspection Phone #: ###-#### Inspection requested via web by Eric Schroeder....finalling permit...is for underground to existing service which ID Power does inspection...changing from overhead to underground...proper depth oked by ID Power not Boise City
|
ELE18-01571
| Electrical Rough-In | 8/28/2018 | 8/28/2018 | 8/28/2018 11:29:47 AM | P | PASS |
|
|
Requesting inspection of rough-in wiring work in shop prior to final and cover. Phone #: ###-#### Inspection requested via web by Cameron Craven...rough ok to cover...check at final neutrals and grounds seperated at shop panel
|
ELE18-03085
| Final | 8/27/2018 | 8/28/2018 | 8/28/2018 11:07:46 AM | A | PASS |
|
|
call 30 mins ahead-Clark Phone #: ###-####...finalling out permit...work was done and corrections made by Electrical contractor permit number ELE18-03280
|
ELE18-03280
| Final | 8/27/2018 | 8/28/2018 | 8/28/2018 11:02:41 AM | A | PASS |
|
|
Please call Mitch 30 minutes prior. Phone #: ###-#### Inspection requested via web by Mitch Whited...contractor to take responsibility for work done without an inspection...inspection was done by contractor and code violations per permit ELE18-03085 were fixed...ok to final permit
|
ELE18-03287
| Final | 8/28/2018 | 8/28/2018 | 8/28/2018 10:18:07 AM | P | CANC |
|
|
Ground works inspection Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Inspection cancelled from web by: Eric Schroeder
|
ELE18-03167
| Final | 8/28/2018 | 8/28/2018 | 8/28/2018 9:38:12 AM | P | PASS |
|
|
Chris Phone #: ###-####...UL label and disconnect ok to final
|
ELE18-03272
| Final | 8/27/2018 | 8/28/2018 | 8/28/2018 9:20:43 AM | A | NR |
|
|
Inspection requested via web by Same Electric..
contractor needs to provide access to work done..will reschedule and meet to get access
|
ELE18-00849
| Electrical Rough-In | 8/27/2018 | 8/28/2018 | 8/28/2018 9:01:54 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton...remaining East wall...wallcover complete
|