BLD15-01869
| FIRE-Final Inspection | 8/28/2018 | 8/28/2018 | 8/28/2018 12:53:22 PM | P | PASS |
|
|
Life safety passed. FIre pump and building expansion covered under new permits
Quentin Phone #: ###-####
|
BLD17-03972
| FIRE-Final Inspection | 8/28/2018 | 8/28/2018 | 8/28/2018 10:24:11 AM | P | FAIL |
|
|
Provide small documents, provide exit discharge lighting at Door #2, remove the tape and shipping clip from sprinkler in Storage Room, provide hardware for the glass double doors, provide modified plans that show the actual installation or walls, provide occupant load sign in the approved location.
|
FIR18-00059
| INSP-Final Inspection | 8/27/2018 | 8/28/2018 | 8/28/2018 9:08:20 AM | A | PASS |
|
|
Permit finaled
Contact is Dirk. Phone #: ###-#### Inspection requested via web by Morgan Ahten
|
BLD18-00353
| FIRE-Final Inspection | 8/27/2018 | 8/28/2018 | 8/28/2018 9:04:11 AM | A | FAIL |
|
|
Need the project related fire alarm permit finaled, need exit signs and emergency lights repaired, need sticker at the main exit.
Please call 30 mins ahead of time so I can meet you there. Phone #: ###-#### Inspection requested via web by Gerome Fries
|
FIR18-00369
| INSP-Final Inspection | 8/27/2018 | 8/28/2018 | 8/28/2018 9:02:58 AM | A | FAIL |
|
|
The duct detectors used are not listed for the application. Resubmit an alternate device.
Phone #: ###-#### Inspection requested via web by Sam Ball
|