ELE02-02122
| Final | 8/28/2002 | 8/29/2002 | 8/29/2002 12:00:00 AM | A | PASS |
|
|
allen; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie-front door code is 193 ok 8/29/2002 12:37:08 PM
|
ELE02-02068
| Final | 8/28/2002 | 8/29/2002 | 8/29/2002 12:00:00 AM | A | PASS |
|
|
allen; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie-lock box code is 193 ok 8/29/2002 12:19:16 PM
|
ELE02-02683
| Rough-In Permanent Service | 8/28/2002 | 8/29/2002 | 8/29/2002 12:00:00 AM | A | PASS |
|
|
r/i ok p/s u/g new ok 8/29/2002 1:05:58 PM
|
ELE02-02690
| Rough-In Permanent Service | 8/28/2002 | 8/29/2002 | 8/29/2002 12:00:00 AM | A | FAIL |
|
|
###-#### john cor. posted called nail plates and 11/4, box fill, 314.43 bath rms, 314.20 inside and outside, 210.52 outlet spacing dinning where it meets family rm note u/g for yard light installed by general and not proper depth, requires inspection for cover 8/29/2002 11:43:23 AM
|
ELE02-00004
| Final | 8/28/2002 | 8/29/2002 | 8/29/2002 12:00:00 AM | P | FAIL |
|
|
fn -bill ###-#### cor. and $45.00 reinspection fee due posted called 410.8 clearence closet light, and switch, and timer for whole house fan shall be wired in parallel, not series 8/29/2002 6:29:24 PM
|
ELE02-00333
| Final | 8/28/2002 | 8/29/2002 | 8/29/2002 12:00:00 AM | P | FAIL |
|
|
bill- ###-#### job not ready 8/29/2002 6:27:31 PM
|
ELE02-02255
| Electrical Rough-In | 8/28/2002 | 8/29/2002 | 8/29/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 08/28/2002 at 18:11:48. Contact: ###-####. met with owner see jf for details 8/29/2002 7:28:16 PM
|
ELE02-02432
| Electrical Rough-In | 8/29/2002 | 8/29/2002 | 8/29/2002 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 08/29/2002 at 08:18:37. Contact: ###-####. hard ceilings in 2 kitchen areas ok 8/29/2002 3:30:12 PM
|
ELE02-02690
| Rough-In Permanent Service | 8/29/2002 | 8/29/2002 | 8/29/2002 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 08/29/2002 at 10:12:24. Contact: ###-####. r/i ok
p/s u/g new ok 8/29/2002 2:17:10 PM
|
ELE02-02702
| Electrical Rough-In | 8/29/2002 | 8/29/2002 | 8/29/2002 12:00:00 AM | P | FAIL |
|
|
###-#### cor. posted called 210.52(D) upstairs bath shall be on 20 amp bath rm circuit, 314.20 putside outlet on new deck shall be flush with siding 8/29/2002 3:02:23 PM
|
ELE02-02641
| Electrical Rough-In | 8/29/2002 | 8/29/2002 | 8/29/2002 12:00:00 AM | P | PASS |
|
|
###-#### r/i ok needs outlet old kitchen counter for proper spacing install before final is called for 8/29/2002 5:35:57 PM
|
ELE02-02687
| Permanent Service | 8/29/2002 | 8/29/2002 | 8/29/2002 12:00:00 AM | P | NH |
|
|
###-#### jim notice posted called 8/30/2002 12:14:22 PM
|