Inspections for the day of: Friday, August 29, 2003.
Number of inspections: 7
Percentage of inspections complete: 86 %
Percentage of inspections not complete: 14 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00187 INSP-Final Inspection8/26/20038/26/2003 A 
FIR03-00155 FIR-Aging Inspection8/29/20038/29/20038/29/2003 12:00:00 AM PASS
this building is still under construction 8/29/2003 9:50:20 AM
BLD03-01681 FIRE-Final Inspection8/27/20038/29/20038/29/2003 12:00:00 AMAFAIL
jim; Phone #: ###-#### Internet Inspection Request from: Marc Lileks the east half of the building is not used by this tenant but may be used in the future and the exit system in this area must have exit signs/emergency lighting as it is not separated from the west half; exit doors to openable from the inside without special knowledge; air handler systems over 2000 cfm to have detectors for unit shutdown per plan review notes and will be installed per UMC 608 as no new mechanical work was part of this permit 8/29/2003 9:54:38 AM
BLD03-01324 FIRE-Conference8/29/20038/29/20038/29/2003 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 8/29/2003 at 12:46:40 AM. Contact: ###-####. Troy did the inspection and it is okay to cover areas per conversation with GC 8/29/2003 3:48:52 PM
BLD03-01568 FIRE-Final Inspection8/28/20038/29/20038/29/2003 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 8/28/2003 at 3:46:36 PM. Contact: ###-####. will have the key lock removed from double door for structrual inspector; detectors okay for AHU shutdown 8/29/2003 1:43:37 PM
FIR03-00454 INSP-Sprinkler Rough-in/Hydro8/29/20038/29/20038/29/2003 12:00:00 AMPPART
rick pager; Phone #: ###-#### Internet Inspection Request from: Marc Lileks packing room hydro and rough-in okay; PIV requires monitoring by fire alarm system 8/29/2003 2:36:32 PM
BLD03-01845 FIRE-Conference8/29/20038/29/20038/29/2003 12:00:00 AMPDONE
left correction notice at job site - need smoke detector above panel, manual pull station and audible alarm; the PIV is not monitored by the fire alarm panel 8/29/2003 3:06:49 PM