Inspections for the day of: Monday, August 29, 2005.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02842 Temporary Service8/25/20058/29/20058/29/2005 4:39:26 PMAFAIL
Scheduled by a contractor via Hello! on 8/25/2005 at 2:22:12 PM. Contact: ###-####. called contractor, left message, left corr notice, 312.5 conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no broken parts,50A recpt fee due
ELE05-02843 Temporary Service8/25/20058/29/20058/29/2005 4:38:41 PMAFAIL
Scheduled by a contractor via Hello! on 8/25/2005 at 2:24:04 PM. Contact: ###-####. called elect, left message, left corr notice, 312.5 conductors entering enclosures shall be protected from abrasion, 110.12(C) there shall be no broken parts, 50A recpt. fee due
ELE05-02227 Final8/29/20058/29/20058/29/2005 4:26:17 PMPPASS
Contact Mike Robinson with any questions.; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong called contr to fix so side gfci on outside
ELE05-02417 Final8/29/20058/29/20058/29/2005 4:25:32 PMPPASS
please call for access///eric; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left message, left survey, 210.8(A)(3) and 210.52(E) recpt out back shall be gfci protected
ELE05-02277 Final8/29/20058/29/20058/29/2005 4:23:54 PMPFAIL
olga; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left corr notice, 210.8(A)(3) outdoor recpts shall be gfci protected, 406.5 recpts shall have faceplates installed (master bath), 422.31(B) lock-out for dishwasher shall be provided in panel
ELE05-03139 Temporary Service8/29/20058/29/20058/29/2005 2:42:15 PMPPASS
rick ###-#### t/s u/g n ok
ELE05-02979 Electrical Rough-In8/29/20058/29/20058/29/2005 2:31:05 PMPPASS
shane; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover trench, told contr to add one more gnd rod and to color white wire on 20A ,240v ckt and to call for final
ELE05-03123 Final8/29/20058/29/20058/29/2005 1:57:07 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Dana Moyer see ps
ELE05-02451 Final8/26/20058/29/20058/29/2005 10:02:55 AMAPART
please contact Duane, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters signed occ card, will final later in week.
ELE05-02823 Temporary Service8/25/20058/29/20058/29/2005 9:05:40 AMAPASS
Scheduled by a contractor via Hello! on 8/25/2005 at 2:22:59 PM. Contact: ###-####. called contr, left message, left survey,312.5 conductors entering enclosure shall have abrasion protection. t/s u/g n ok
ELE05-02841 Temporary Service8/27/20058/29/20058/29/2005 8:39:18 AMAPASS
Scheduled by a contractor via Hello! on 8/27/2005 at 7:53:03 AM. Contact: ###-####. corrections made, t/s u/g n ok
ELE05-02824 Temporary Service8/27/20058/29/20058/29/2005 8:30:52 AMAPASS
Scheduled by a contractor via Hello! on 8/27/2005 at 7:53:56 AM. Contact: ###-####. corrections made, t/s u/g n ok
ELE05-03128 Electrical Rough-In8/26/20058/29/20058/29/2005 8:03:01 AMACANC
###-#### - clyde see rip
ELE05-03128 Rough-In Permanent Service8/29/20058/29/20058/29/2005 12:00:00 AMAPASS
###-#### - clyde called contr about cable jacketing and gec. ric ok, p/s u/g n ok
ELE05-03123 Permanent Service8/29/20058/29/20058/29/2005 12:00:00 AMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer p/s u/g n ok