ELE05-02842
| Temporary Service | 8/25/2005 | 8/29/2005 | 8/29/2005 4:39:26 PM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/25/2005 at 2:22:12 PM. Contact: ###-####. called contractor, left message, left corr notice, 312.5 conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no broken parts,50A recpt fee due
|
ELE05-02843
| Temporary Service | 8/25/2005 | 8/29/2005 | 8/29/2005 4:38:41 PM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/25/2005 at 2:24:04 PM. Contact: ###-####. called elect, left message, left corr notice, 312.5 conductors entering enclosures shall be protected from abrasion, 110.12(C) there shall be no broken parts, 50A recpt. fee due
|
ELE05-02227
| Final | 8/29/2005 | 8/29/2005 | 8/29/2005 4:26:17 PM | P | PASS |
|
|
Contact Mike Robinson with any questions.; Phone #: ###-#### Internet Inspection Request from: Shelli Daylong called contr to fix so side gfci on outside
|
ELE05-02417
| Final | 8/29/2005 | 8/29/2005 | 8/29/2005 4:25:32 PM | P | PASS |
|
|
please call for access///eric; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left message, left survey, 210.8(A)(3) and 210.52(E) recpt out back shall be gfci protected
|
ELE05-02277
| Final | 8/29/2005 | 8/29/2005 | 8/29/2005 4:23:54 PM | P | FAIL |
|
|
olga; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, left corr notice, 210.8(A)(3) outdoor recpts shall be gfci protected, 406.5 recpts shall have faceplates installed (master bath), 422.31(B) lock-out for dishwasher shall be provided in panel
|
ELE05-03139
| Temporary Service | 8/29/2005 | 8/29/2005 | 8/29/2005 2:42:15 PM | P | PASS |
|
|
rick ###-#### t/s u/g n ok
|
ELE05-02979
| Electrical Rough-In | 8/29/2005 | 8/29/2005 | 8/29/2005 2:31:05 PM | P | PASS |
|
|
shane; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover trench, told contr to add one more gnd rod and to color white wire on 20A ,240v ckt and to call for final
|
ELE05-03123
| Final | 8/29/2005 | 8/29/2005 | 8/29/2005 1:57:07 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer see ps
|
ELE05-02451
| Final | 8/26/2005 | 8/29/2005 | 8/29/2005 10:02:55 AM | A | PART |
|
|
please contact Duane, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters signed occ card, will final later in week.
|
ELE05-02823
| Temporary Service | 8/25/2005 | 8/29/2005 | 8/29/2005 9:05:40 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 8/25/2005 at 2:22:59 PM. Contact: ###-####. called contr, left message, left survey,312.5 conductors entering enclosure shall have abrasion protection. t/s u/g n ok
|
ELE05-02841
| Temporary Service | 8/27/2005 | 8/29/2005 | 8/29/2005 8:39:18 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 8/27/2005 at 7:53:03 AM. Contact: ###-####. corrections made, t/s u/g n ok
|
ELE05-02824
| Temporary Service | 8/27/2005 | 8/29/2005 | 8/29/2005 8:30:52 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 8/27/2005 at 7:53:56 AM. Contact: ###-####. corrections made, t/s u/g n ok
|
ELE05-03128
| Electrical Rough-In | 8/26/2005 | 8/29/2005 | 8/29/2005 8:03:01 AM | A | CANC |
|
|
###-#### - clyde see rip
|
ELE05-03128
| Rough-In Permanent Service | 8/29/2005 | 8/29/2005 | 8/29/2005 12:00:00 AM | A | PASS |
|
|
###-#### - clyde called contr about cable jacketing and gec. ric ok, p/s u/g n ok
|
ELE05-03123
| Permanent Service | 8/29/2005 | 8/29/2005 | 8/29/2005 12:00:00 AM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer p/s u/g n ok
|