FIR05-00411
| INSP-Final Inspection | 8/26/2005 | 8/29/2005 | 8/29/2005 5:06:18 PM | P | PASS |
|
|
Fire alarm passed inspection.
|
BLD05-00347
| FIRE-Final Inspection | 8/24/2005 | 8/29/2005 | 8/29/2005 4:20:22 PM | P | PART |
|
|
Temporary occupancy for the office area within scope of work is approved per Jenifer Gililland and Troy Cobbley pending a racking permit for the adjacent warehouse.
|
MIS05-00115
| FIR-Final | 8/26/2005 | 8/29/2005 | 8/29/2005 4:13:38 PM | P | CANC |
|
|
No time today for this inspection, spoke with John at ###-####, he will reschedule for 8/31/05 a.m. per our agreement.
|
BLD05-00232
| FIRE-Final Inspection | 8/26/2005 | 8/29/2005 | 8/29/2005 3:45:25 PM | P | FAIL |
|
|
Locate building address to face Bown Way, provide fire extinguisher on the upstairs level, verify door hardware after installation.
|
MIS05-00135
| FIR-Final | 8/29/2005 | 8/29/2005 | 8/29/2005 3:15:28 PM | P | FAIL |
|
|
Provide exit sign and emergency lighting at restroom corridor as discussed, provide current annual inspection on fire sprinkler system, remove locking hardware at exit door from restroom corridor.
|
FIR05-00394
| INSP-Final Inspection | 8/26/2005 | 8/29/2005 | 8/29/2005 1:56:09 PM | P | NR |
|
|
Cancel inspection per Grant with Protex, not ready for inspection.
|
BLD05-00127
| FIRE-Final Inspection | 8/29/2005 | 8/29/2005 | 8/29/2005 1:55:01 PM | P | FAIL |
|
|
Remove locking hardware at SW door, provide additional fire extinguisher as discussed.
|
FIR04-00737
| INSP-Sprinkler Rough-in/Hydro | 8/29/2005 | 8/29/2005 | 8/29/2005 1:23:06 PM | P | PART |
|
|
Re-hydrostatic test of the dry system passed inspection.
|
FIR05-00044
| INSP-Final Inspection | 8/26/2005 | 8/29/2005 | 8/29/2005 12:58:52 PM | A | NR |
|
|
Inspection is scheduled for 8/30 at 12:00 noon.
|
FIR05-00303
| INSP-Final Inspection | 8/26/2005 | 8/29/2005 | 8/29/2005 12:43:34 PM | P | PASS |
|
|
Hood suppression system operated correctly under test conditions, permit finaled.
|
FIR05-00155
| INSP-Final Inspection | 8/26/2005 | 8/29/2005 | 8/29/2005 12:06:17 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
MIS05-00125
| FIR-Final | 8/25/2005 | 8/29/2005 | 8/29/2005 10:32:52 AM | A | FAIL |
|
|
Provide fire extinguishers, repair emergency lighting and exit signs, provide max occupant load sign, provide city permit documents at next inspection.
|
FIR05-00393
| INSP-Sprinkler Rough-in/Hydro | 8/26/2005 | 8/29/2005 | 8/29/2005 10:06:47 AM | A | PART |
|
|
Overhead rough in is satisfactory, will final permit when ceiling tile has been installed.
|
BLD05-01311
| FIRE-Final Inspection | 8/26/2005 | 8/29/2005 | 8/29/2005 9:31:48 AM | A | PASS |
|
|
Fire life safety passed inspection, hospital to post "No Smoking" signs per the GC.
|
FIR05-00338
| INSP-Sprinkler Rough-in | 8/26/2005 | 8/29/2005 | 8/29/2005 9:29:49 AM | A | FAIL |
|
|
Underground fire supply line installation does not match the approved drawings. Need to resubmit plans reflecting added 45's and change of directions for approval prior to field inspection. In addition, the minimum 4'-6" depth of bury is not met in several locations.
|