FIR05-00176
| INSP-Final Inspection | 8/29/2006 | 8/29/2006 | 8/29/2006 4:35:21 PM | P | PASS |
|
|
UG fire sprinkler supply line permit finaled.
|
FIR06-00432
| INSP-Final Inspection | 8/28/2006 | 8/29/2006 | 8/29/2006 4:34:24 PM | P | FAIL |
|
|
Buildings C and D are missing spare heads in the head boxes at the riser, also all four building systems are overdue the required annual inspection to be performed by a licensed fire sprinkler contractor.
|
BLD04-00947
| FIRE-Final Inspection | 8/28/2006 | 8/29/2006 | 8/29/2006 4:28:32 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
BLD06-01932
| FIRE-Final Inspection | 8/28/2006 | 8/29/2006 | 8/29/2006 1:42:18 PM | A | FAIL |
|
|
The project related fire sprinkler and fire alarm permits must be inspected, approved and finaled prior to BLD life safety final. Noted manual thumbturn to be removed at office door.
|
BLD06-01932
| FIRE-Sprinkler Rough-in | 8/28/2006 | 8/29/2006 | 8/29/2006 1:40:00 PM | A | PART |
|
|
Inspection request was for the fire sprinklers which needs to be called in under the appropriate FIR permit number. Noted that OH rough-in is satisfactory, need to provide a current annual inspection certification for the existing system riser.
|