Inspections for the day of: Tuesday, August 29, 2006.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00176 INSP-Final Inspection8/29/20068/29/20068/29/2006 4:35:21 PMPPASS
UG fire sprinkler supply line permit finaled.
FIR06-00432 INSP-Final Inspection8/28/20068/29/20068/29/2006 4:34:24 PMPFAIL
Buildings C and D are missing spare heads in the head boxes at the riser, also all four building systems are overdue the required annual inspection to be performed by a licensed fire sprinkler contractor.
BLD04-00947 FIRE-Final Inspection8/28/20068/29/20068/29/2006 4:28:32 PMAPASS
Fire life safety inspection passed.
BLD06-01932 FIRE-Final Inspection8/28/20068/29/20068/29/2006 1:42:18 PMAFAIL
The project related fire sprinkler and fire alarm permits must be inspected, approved and finaled prior to BLD life safety final. Noted manual thumbturn to be removed at office door.
BLD06-01932 FIRE-Sprinkler Rough-in8/28/20068/29/20068/29/2006 1:40:00 PMAPART
Inspection request was for the fire sprinklers which needs to be called in under the appropriate FIR permit number. Noted that OH rough-in is satisfactory, need to provide a current annual inspection certification for the existing system riser.