Inspections for the day of: Tuesday, August 29, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00643 INSP-Final Inspection8/28/20068/29/20068/29/2006 4:34:36 PMPPASS
Hood suppression system operated correctly
FIR06-00616 INSP-Sprinkler Rough-in8/29/20068/29/20068/29/2006 4:34:08 PMPPART
Underground supply piping from the united water connection to the first 90 is ok to cover. The first 90 and the thrust block has not been installed yet.
FIR06-00617 INSP-Sprinkler Rough-in8/29/20068/29/20068/29/2006 4:33:48 PMPPART
Underground supply piping from the united water connection to the first 90 is ok to cover. The first 90 and the thrust block has not been installed yet.
FIR06-00625 INSP-Final Inspection8/28/20068/29/20068/29/2006 4:32:42 PMPPASS
Sprinkler piping is ok to cover. Two additional pendants have been provided to correct sprinkler spacing.
FIR06-00452 INSP-Final Inspection8/29/20068/29/20068/29/2006 4:30:25 PMPPASS
permit finaled
FIR05-00536 INSP-Sprinkler Rough-in/Hydro8/29/20068/29/20068/29/2006 12:59:35 PMPPASS
Hydro test of the west standpipe passed and can be covered in the first floor and basement walls.
MIS06-00210 FIR-Final8/23/20068/29/20068/29/2006 12:56:06 PMAPART
A temporary occupancy was given until the fire extinguisher is mounted, the address is provided, the sticker is provided at the main exit, lever hardware at the main exit is provided and the thumbturn is removed.
MIS05-00181 FIR-Final8/29/20068/29/20068/29/2006 11:51:36 AMPPASS
Life safety finaled.
FIR06-00218 INSP-Sprinkler Rough-in/Hydro8/28/20068/29/20068/29/2006 11:44:30 AMAPASS
The remaining piping on the first floor is ok to cover. Two additional upright sprinkler heads are required as discussed due to duct blockage. Their placement will be verified at the final.
FIR06-00409 INSP-Supply line flush8/28/20068/29/20068/29/2006 9:34:27 AMAPASS
Underground flush passed.