ELE07-02688
| Electrical Rough-In | 8/29/2007 | 8/29/2007 | 8/29/2007 2:53:05 PM | P | FAIL |
|
|
Rough In Inspection. Please call Brian T. @ ###-####. Phone #: ###-#### Internet Inspection Request from: todd hall corr. met contr. 300.4(D) 11/4" for cables parallel, 330.30(B) secure cables 12" of boxes, 352.24&110.3(A) replace damaged u/g pvc, 358.30(A) secure emt within 3ft of boxes
|
ELE07-02699
| Final | 8/29/2007 | 8/29/2007 | 8/29/2007 1:50:02 PM | P | FAIL |
|
|
Jeff; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr. called 410.8 clearence SW closet light, 408.4 be specific pane shedule left message
|
ELE07-02701
| Final | 8/29/2007 | 8/29/2007 | 8/29/2007 1:24:43 PM | P | PASS |
|
|
Jeff; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok survey posted called 408.4 be specific purpose and use
|
ELE07-03008
| Temporary Service | 8/29/2007 | 8/29/2007 | 8/29/2007 12:43:10 PM | P | FAIL |
|
|
thank you Phone #: ###-#### Internet Inspection Request from: Tracy Robertson corr called 590.6(B)(1) needs gfci breaker for 240V recept
|
ELE07-03010
| Temporary Service | 8/29/2007 | 8/29/2007 | 8/29/2007 12:42:12 PM | P | FAIL |
|
|
Thank you Phone #: ###-#### Internet Inspection Request from: Tracy corr called 590.6(B)(1) needs gfci breaker for 240 V recept
|
ELE07-03013
| Temporary Service | 8/29/2007 | 8/29/2007 | 8/29/2007 12:32:19 PM | P | PASS |
|
|
Thank you Phone #: ###-#### Internet Inspection Request from: Tracy Robertson t/s u/g new ok
|
ELE07-03011
| Temporary Service | 8/29/2007 | 8/29/2007 | 8/29/2007 12:31:55 PM | P | PASS |
|
|
thank you Phone #: ###-#### Internet Inspection Request from: Tracy Robertson t/s u/g new ok
|
ELE07-03012
| Temporary Service | 8/29/2007 | 8/29/2007 | 8/29/2007 12:31:31 PM | P | PASS |
|
|
thank you Phone #: ###-#### Internet Inspection Request from: Tracy Robertson t/s u/g new ok
|
ELE06-01438
| Final | 8/28/2007 | 8/29/2007 | 8/29/2007 10:28:51 AM | A | FAIL |
|
|
daniel - please call 1/2 hr prior to inspection Phone #: ###-#### not ready
|
ELE06-04230
| Final | 8/28/2007 | 8/29/2007 | 8/29/2007 9:37:15 AM | A | FAIL |
|
|
Final - pls call Michelle w/Gammill @ ###-#### 30min prior for access. Scheduled by Heather w/Doherty Phone #: ###-#### Internet Inspection Request from: Heather Packer called Jim with doherty, need access to jtub receptacle cannot get tester in it to check for gfci
|
ELE06-02298
| Final | 8/28/2007 | 8/29/2007 | 8/29/2007 8:46:32 AM | A | FAIL |
|
|
Marv; Phone #: ###-#### Internet Inspection Request from: Hattie James corr not made and no power meter not set
|
ELE07-01473
| Final | 8/28/2007 | 8/29/2007 | 8/29/2007 8:11:10 AM | A | NH |
|
|
Chris; Phone #: ###-#### Internet Inspection Request from: Hattie James card posted
|
ELE07-03003
| Temporary Service | 8/28/2007 | 8/29/2007 | 8/28/2007 12:57:37 PM | A | PASS |
|
|
gene Phone #: ###-#### t/s u/g new ok
|