BLD07-00057
| FIRE-Final Inspection | 8/29/2007 | 8/29/2007 | 8/29/2007 5:15:08 PM | P | CANC |
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
BLD07-00959
| FIRE-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 5:14:12 PM | P | CANC |
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
FIR07-00501
| INSP-Sprinkler Rough-in/Hydro | 8/28/2007 | 8/29/2007 | 8/29/2007 4:58:08 PM | P | CANC |
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
FIR05-00536
| INSP-Final Inspection | 8/29/2007 | 8/29/2007 | 8/29/2007 4:42:33 PM | P | CANC |
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
BLD06-03088
| FIRE-Final Inspection | 8/29/2007 | 8/29/2007 | 8/29/2007 4:41:10 PM | P | CANC |
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
FIR07-00732
| INSP-Sprinkler Rough-in | 8/28/2007 | 8/29/2007 | 8/29/2007 4:24:03 PM | A | PASS |
|
|
Todd; Phone #: ###-#### Internet Inspection Request from: Hattie James
|
FIR07-00502
| INSP-Supply line flush | 8/28/2007 | 8/29/2007 | 8/29/2007 4:07:06 PM | A | PASS |
|
|
Underground supply flush passed.
|
BLD07-00804
| FIRE-Final Inspection | 8/29/2007 | 8/29/2007 | 8/29/2007 3:46:08 PM | P | CANC |
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
FIR07-00620
| INSP-Sprinkler Rough-in | 8/29/2007 | 8/29/2007 | 8/29/2007 3:40:30 PM | P | CANC |
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
FIR07-00554
| INSP-Sprinkler Rough-in | 8/28/2007 | 8/29/2007 | 8/29/2007 3:38:38 PM | P | CANC |
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
FIR06-00011
| INSP-Alarm Testing | 8/29/2007 | 8/29/2007 | 8/29/2007 3:32:48 PM | P | CANC |
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
FIR07-00441
| INSP-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 3:31:12 PM | P | CANC |
|
|
sandy Phone #: ###-####Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
FIR07-00220
| INSP-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 3:29:21 PM | A | CANC |
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
FIR07-00511
| INSP-Sprinkler Rough-in | 8/28/2007 | 8/29/2007 | 8/29/2007 3:25:39 PM | A | CANC |
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
FIR07-00437
| INSP-Sprinkler Rough-in | 8/28/2007 | 8/29/2007 | 8/29/2007 3:21:30 PM | A | CANC |
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
FIR07-00690
| INSP-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 3:19:28 PM | A | FAIL |
|
|
The fire alarm contractor and I could not get the heat to come on. Per the hvac contractor the valve might be turned off and he also stated that he did not think that the hvac unit was wired to shut down immediately which I notified them was required. No test performed.
|
BLD07-01662
| FIRE-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 3:15:51 PM | A | PASS |
|
|
life safety passed.
|
FIR07-00502
| INSP-Sprinkler Rough-in/Hydro | 8/28/2007 | 8/29/2007 | 8/29/2007 3:13:53 PM | A | PASS |
|
|
The underground hydro test passed.
|
FIR07-00712
| INSP-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 3:10:03 PM | A | CANC |
|
|
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.
|
FIR07-00674
| INSP-Sprinkler Rough-in/Hydro | 8/27/2007 | 8/29/2007 | 8/29/2007 1:38:09 PM | A | FAIL |
|
|
Provide verification that the 1/2" piping to the sprinkler heads and the tape separation on the piping/hangers was allowed under the code in which the buidling was built. See the city approved plans for locations where sprinkler heads need to be changed from 200 to 155 degrees. Also see the plans where the clouded area is the only area not inspected.
|
FIR07-00560
| INSP-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 1:25:18 PM | A | PASS |
|
|
Permit finaled
|
BLD07-01374
| FIRE-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 1:23:29 PM | A | PASS |
|
|
Life safety passed
|
FIR07-00720
| INSP-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 12:06:51 PM | A | PASS |
|
|
Permit finaled
|
FIR07-00548
| INSP-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 12:05:26 PM | A | PASS |
|
|
Permit finaled
|
BLD07-01532
| FIRE-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 10:07:05 AM | A | FAIL |
|
|
Remove the dead bolt from the rear door, provide the correct size fire extinguisher and provide a sticker at the main exit.
|
BLD07-01533
| FIRE-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 10:05:59 AM | A | PASS |
|
|
LIfe safety passed
|
BLD07-01710
| FIRE-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 9:32:27 AM | A | FAIL |
|
|
I can't determine what the maximum storage height is for the racking. I will need the city approved sprinkler plans for that information.
|
BLD06-00943
| FIRE-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 8:42:46 AM | A | PASS |
|
|
life safety passed
|
BLD07-01107
| FIRE-Final Inspection | 8/28/2007 | 8/29/2007 | 8/29/2007 8:26:34 AM | A | PASS |
|
|
Life safety passed
|