ELE08-01435
| ELE-Aging Inspection | 8/29/2008 | 8/29/2008 | 9/2/2008 12:31:34 PM | | DONE |
|
|
|
ELE08-01015
| ELE-Aging Inspection | 8/29/2008 | 8/29/2008 | 8/29/2008 3:49:58 PM | | PART |
|
|
wsuc
|
ELE08-02393
| Conference | 8/29/2008 | 8/29/2008 | 8/29/2008 3:49:31 PM | P | DONE |
|
|
Andy- call 20 min prior to going Phone #: ###-#### ok
|
ELE08-02142
| Electrical Rough-In | 8/28/2008 | 8/29/2008 | 8/29/2008 3:49:13 PM | A | FAIL |
|
|
Rough-in/ temp. occupancy Phone #: ###-#### Internet Inspection Request from: Jenni Keller 110.2, BCC 4.05.33 (A) all equipment shall be labeled and listed, told owner all he wanted was to argue, corr posted partial corr only too many violations noted NEC articles 450,250,240, 314, 110.26 all wiring shall meet 2008 NEC no violations retained
|
ELE08-02409
| Electrical Rough-In | 8/28/2008 | 8/29/2008 | 8/29/2008 2:41:53 PM | A | FAIL |
|
|
This will be for the rough-in on electrical only. Mark Hood will be the contact person. Thank you Phone #: ###-#### Internet Inspection Request from: Laura Longshaw corr BCC owner installed and covered u/g no permit or inspection, 356.42 use fittings listed for LFNC not jakes and shall be listed for concrete, and encased 110.12(A) seal all unused KOs, 300.4 nail plates and 11/4" for raceways and cables also needs grd pigtails for switches called partial correction notice only
|
ELE08-01419
| Final | 8/28/2008 | 8/29/2008 | 8/29/2008 1:45:56 PM | P | PART |
|
|
Hi Jack, We are ready for the temp. final for this project (this is the one without UL listings on the presses, that is why we need a temp.), according to the owner the UL inspectors are scheduled to come here around the end of September, but I don''t have an exact date. Mucho should be on site, if you can''t find him his cell number is ###-####. Give me a call if you have any questions. t/o ok card signed note needs all equipment to be labeled and listed Thx. Wayne Phone #: ###-#### Internet Inspection Request from: Wayne Craig
|
ELE08-02070
| Final | 8/28/2008 | 8/29/2008 | 8/29/2008 12:07:31 PM | A | PASS |
|
|
Jim Phone #: ###-#### ok card signed
|
ELE08-02009
| Electrical Rough-In | 8/28/2008 | 8/29/2008 | 8/29/2008 11:49:28 AM | A | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Bryan McLaughlin hard ceilings anop
|