BLD08-01433
| FIRE-Final Inspection | 8/28/2008 | 8/29/2008 | 8/29/2008 4:26:25 PM | A | PASS |
|
|
Noted correction items have been repaired, fire life safety finaled.
|
BLD08-01021
| FIRE-Final Inspection | 8/28/2008 | 8/29/2008 | 8/29/2008 4:24:33 PM | A | PASS |
|
|
Fire life safety passed inspection, door closure at one location to be reinstalled when move is finished.
|
FIR08-00433
| INSP-Sprinkler Rough-in | 8/28/2008 | 8/29/2008 | 8/29/2008 4:22:45 PM | P | PART |
|
|
UG fire supply line stub out including the tee connection and thrust block are okay for cover, bedding material to be provided as discussed.
|
FIR08-00045
| INSP-Sprinkler Rough-in | 8/29/2008 | 8/29/2008 | 8/29/2008 4:20:29 PM | P | FAIL |
|
|
On site visit to confirm notes per last inspection completed 8/19. Dry upright sprinkler coverage is overspaced or missing at several locations, noted several field modifications which will necessitate resubmitted plans matching the installation.
|
FIR08-00492
| INSP-Final Inspection | 8/29/2008 | 8/29/2008 | 8/29/2008 4:16:17 PM | P | PASS |
|
|
Scope of fire sprinkler permit work finaled.
|
FIR08-00482
| INSP-Final Inspection | 8/28/2008 | 8/29/2008 | 8/29/2008 4:15:29 PM | A | PASS |
|
|
Fire sprinkler final field inspection passed.
|
FIR08-00499
| INSP-Final Inspection | 8/28/2008 | 8/29/2008 | 8/29/2008 4:14:37 PM | A | PASS |
|
|
Fire alarm testing completed satisfactory, permit finaled.
|
FIR08-00364
| FIR-Aging Inspection | 8/29/2008 | 8/29/2008 | 8/29/2008 4:13:49 PM | | DONE |
|
|
On site visit with general contractor regarding status of work, waiting for phone lines to be installed prior to fire alarm testing.
|
BLD08-01159
| FIRE-Final Inspection | 8/28/2008 | 8/29/2008 | 8/29/2008 4:12:14 PM | A | PASS |
|
|
Fire life safety inspection passed.
|
BLD07-02977
| FIRE-Final Inspection | 8/28/2008 | 8/29/2008 | 8/29/2008 4:11:19 PM | A | PASS |
|
|
Vanilla fire life safety finaled.
|
FIR08-00495
| INSP-Final Inspection | 8/29/2008 | 8/29/2008 | 8/29/2008 4:10:40 PM | A | PASS |
|
|
Final fire sprinkler inspection completed acceptable, permit finaled.
|
FIR08-00488
| INSP-Final Inspection | 8/28/2008 | 8/29/2008 | 8/29/2008 4:09:57 PM | A | PASS |
|
|
Fire alarm field testing passed, permit finaled.
|
FIR07-01036
| INSP-Final Inspection | 8/28/2008 | 8/29/2008 | 8/29/2008 4:08:55 PM | A | PASS |
|
|
Fire alarm permit finaled.
|