Inspections for the day of: Wednesday, August 29, 2012.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00451 INSP-Conference8/28/20128/29/20129/5/2012 1:54:43 PMADONE
On site conference with contractor regarding sprinkler coverage at exterior canopies to meet the guidelines and requirements of NFPA 13 2010 sections 8.15.7.1, 8.15.7.2, 8.15.7.3, and 8.15.7.5. Any alternate proposals or methods to these conditions must be approved by the fire code official per IFC 2009 104.9.
FIR12-00246 INSP-Sprinkler Rough-in8/29/20128/29/20128/30/2012 3:03:22 PMPPART
Okay to cover pendent and SW heads above the sheetrock ceilings at the east wing resident rooms.
FIR11-00665 INSP-Final Inspection8/29/20128/29/20128/29/2012 4:16:24 PMAPASS
FIR10-00622 INSP-Final Inspection8/29/20128/29/20128/29/2012 4:15:23 PMAPASS
FIR12-00261 INSP-Final Inspection8/29/20128/29/20128/29/2012 4:14:59 PMAPASS
FIR12-00466 INSP-Final Inspection8/28/20128/29/20128/29/2012 3:33:53 PMAPASS
Fire sprinkler work passed final inspection.
BLD12-02067 FIRE-Final Inspection8/29/20128/29/20128/29/2012 2:21:50 PMPPASS
Fire life safety inspection passed.
FIR12-00430 INSP-Final Inspection8/29/20128/29/20128/29/2012 2:20:41 PMPPASS
Scope of work is finished. Fire sprinkler permit finaled.
FIR12-00264 INSP-Supply line flush8/28/20128/29/20128/29/2012 2:19:22 PMPPART
UG fire supply line flush completed satisfactory.
FIR12-00451 INSP-Sprinkler Rough-in8/28/20128/29/20128/29/2012 2:18:08 PMAPART
Overhead work at the second floor elevator machine room and four office rooms okayed for ceiling cover, also approved rough-in at the new 2" branch line and drops to the produce cooler and ceilings in the specialty area.
FIR12-00340 INSP-Final Inspection8/28/20128/29/20128/29/2012 2:12:42 PMAPASS
Fire alarm permit finaled. Inspection passed.
FIR12-00458 INSP-Final Inspection8/27/20128/29/20128/29/2012 2:10:39 PMAPASS
Fire alarm work passed test and inspection. Permit final approved.
BLD12-00812 FIRE-Final Inspection8/28/20128/29/20128/29/2012 2:09:12 PMAPASS
Scope of work at the Jesse Tree office area passed life safety with the exception of hardware at the RR pocket door to be revised prior to structural final as discussed.
FIR12-00439 INSP-Final Inspection8/28/20128/29/20128/29/2012 2:07:04 PMAPASS
Fire sprinkler permit finaled.
FIR06-00385 FIR-Aging Inspection8/29/20128/29/20128/29/2012 11:00:47 AM DEFR
FIR05-00238 FIR-Aging Inspection8/29/20128/29/20128/29/2012 11:00:16 AM DEFR
FIR07-00315 FIR-Aging Inspection8/29/20128/29/20128/29/2012 10:59:48 AM DEFR