ELE12-01772
| Final | 8/29/2012 | 8/29/2012 | 8/29/2012 3:16:03 PM | P | FAIL |
|
|
Please provide a final inspection. Contact Cody ###-####. Have a great day!! Phone #: ###-#### >> Inspection requested via web by Kevin Perez. NEC 210.8 B5 GFCI receptacles within 6 ft of sink.
|
ELE12-02163
| Electrical Rough-In | 8/28/2012 | 8/29/2012 | 8/29/2012 2:51:29 PM | P | PASS |
|
|
Bonding--Roy Phone #: ###-####
|
ELE12-00059
| Final | 8/28/2012 | 8/29/2012 | 8/29/2012 2:19:35 PM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Matthew White. NEC 352.30 A Need to strap both conduits. Earth is not considered first support. Ground can settle and pull pipe and connector apart.
|
ELE12-00065
| Final | 8/28/2012 | 8/29/2012 | 8/29/2012 2:19:15 PM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Matthew White. NEC 352.30 A Need to strap both conduits. Earth is not considered first support. Ground can settle and pull pipe and connector apart.
|
ELE12-02158
| Temporary Service | 8/28/2012 | 8/29/2012 | 8/29/2012 2:00:03 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Zane Robertson.T/S Connect ok. please notify serviceman that there is a wasp nest in meter section. Thx
|
ELE12-01841
| Electrical Rough-In | 8/29/2012 | 8/29/2012 | 8/29/2012 1:25:45 PM | P | PASS |
|
|
Underground on inside. Danny is contact Phone #: ###-#### >> Inspection requested via web by Buster Bowen. Underground inside for service.
|