FIR13-00163
| INSP-Final Inspection | 8/28/2013 | 8/29/2013 | 8/30/2013 10:01:27 AM | P | PASS |
|
|
Permit finaled
|
FIR12-00648
| INSP-Final Inspection | 8/29/2013 | 8/29/2013 | 8/29/2013 3:24:14 PM | P | FAIL |
|
|
See the city approved plans for corrections noted. They include overspaced strobes, need for an additional strobe in a corridor, tamper switch/supervisory signal text at panel and central station needing modified so it does not say "waterflow", water turned on so the flow switch can be tested, signage at the facp door, map at the facp, knox box....ect.
|
FIR13-00291
| INSP-Final Inspection | 8/28/2013 | 8/29/2013 | 8/29/2013 1:58:20 PM | A | PASS |
|
|
Permit finaled
|
FIR13-00086
| INSP-Final Inspection | 8/28/2013 | 8/29/2013 | 8/29/2013 1:54:03 PM | A | FAIL |
|
|
See the city approved plans for locations where strobes need to be relocated due to being overspaced and mounted outside of their listing. Additional devices will be required in acouple of locations. No testing of the a/v devices took place.
|
FIR12-00695
| INSP-Sprinkler Rough-in | 8/28/2013 | 8/29/2013 | 8/29/2013 1:52:21 PM | A | PASS |
|
|
See the city approved plans for new areas where piping is ok to cover.
|
BLD13-02175
| FIRE-Conference | 8/28/2013 | 8/29/2013 | 8/29/2013 12:05:31 PM | A | DONE |
|
|
Sprinkler heads in soffit are ok.
|