Inspections for the day of: Thursday, August 29, 2013.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00163 INSP-Final Inspection8/28/20138/29/20138/30/2013 10:01:27 AMPPASS
Permit finaled
FIR12-00648 INSP-Final Inspection8/29/20138/29/20138/29/2013 3:24:14 PMPFAIL
See the city approved plans for corrections noted. They include overspaced strobes, need for an additional strobe in a corridor, tamper switch/supervisory signal text at panel and central station needing modified so it does not say "waterflow", water turned on so the flow switch can be tested, signage at the facp door, map at the facp, knox box....ect.
FIR13-00291 INSP-Final Inspection8/28/20138/29/20138/29/2013 1:58:20 PMAPASS
Permit finaled
FIR13-00086 INSP-Final Inspection8/28/20138/29/20138/29/2013 1:54:03 PMAFAIL
See the city approved plans for locations where strobes need to be relocated due to being overspaced and mounted outside of their listing. Additional devices will be required in acouple of locations. No testing of the a/v devices took place.
FIR12-00695 INSP-Sprinkler Rough-in8/28/20138/29/20138/29/2013 1:52:21 PMAPASS
See the city approved plans for new areas where piping is ok to cover.
BLD13-02175 FIRE-Conference8/28/20138/29/20138/29/2013 12:05:31 PMADONE
Sprinkler heads in soffit are ok.