Inspections for the day of: Friday, August 29, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00555 INSP-Sprinkler Rough-in/Hydro8/29/20148/29/20148/29/2014 3:01:37 PMPPASS
Underground supply piping is ok to cover
FIR14-00566 INSP-Final Inspection8/28/20148/29/20148/29/2014 3:00:18 PMAFAIL
Ran out of smoke and lost connection with the computer to verify signals. To be rescheduled for tuesday morning.
FIR14-00248 INSP-Final Inspection8/29/20148/29/20148/29/2014 2:19:41 PMPCANC
Cancel per Tom Phone #: ###-####
FIR14-00357 INSP-Sprinkler Rough-in8/29/20148/29/20148/29/2014 2:18:53 PMPPASS
Rough-in passed. Piping can not be covered until a tenting inspection has been passed.
FIR14-00356 INSP-Sprinkler Rough-in8/29/20148/29/20148/29/2014 2:18:01 PMPPASS
Piping rough-in passed. Piping can not be covered until the tenting has been corrected.
FIR14-00356 INSP-Sprinkler Rough-in/Hydro8/29/20148/29/20148/29/2014 2:17:21 PMPCANC
Riser is not built yet so not ready for hydro test. Will be rescheduled.
BLD14-01713 FIRE-Final Inspection8/29/20148/29/20148/29/2014 1:27:50 PMPPASS
life safety passed
FIR14-00405 INSP-Final Inspection8/28/20148/29/20148/29/2014 10:17:40 AMAFAIL
Phone #: ###-####, I left message on contacts voice mail that I was on the way. Arrived at project, could not find contact and security guard knew nothing. No inspection performed.
BLD14-01743 FIRE-Final Inspection8/28/20148/29/20148/29/2014 9:50:36 AMAFAIL
Pendant head is overspaced . Work will require a permit. Life safety will be ok to final when completed.
FIR14-00581 INSP-Sprinkler Rough-in8/28/20148/29/20148/29/2014 9:23:59 AMAPART
Inspection turned into a conference. I noted, and we discussed, the extensive amount of obstructions caused by mechanical duct work. It does not appear that any of the obstruction rules for the CC heads can be met and that additional sprinkler heads will be required. With additional heads hydraulic calculations/pipe routing will/could be effected and plan modifications required. I also noted that the area under the stairs is combustible and does not have sprinkler protection. This will require special consideration to meet NFPA 13 requirements prior to a cover inspection.
BLD14-01764 FIRE-Supply Line Cover8/28/20148/29/20148/29/2014 9:19:35 AMACANC
Wrong inspection type called in.
FIR14-00589 INSP-Final Inspection8/28/20148/29/20148/29/2014 9:05:04 AMACANC
call 1/2 hour prior please...###-#### Phone #: ###-#### >> Inspection requested via web by Rick Groom Inspection cancelled from web by: Rick Groom