ELE11-01478
| ELE-Aging Inspection | 8/29/2016 | 8/29/2016 | 8/29/2016 2:47:19 PM | | DONE |
|
|
too busy
|
ELE16-02748
| Rough-In Permanent Service | 8/29/2016 | 8/29/2016 | 8/29/2016 2:46:44 PM | P | CANC |
|
|
Door code CAM, if you have any questions, please call the lead on the job, Luke at ###-####. Thank you!! Phone #: ###-#### Inspection requested via web by Clay Morgan see ri
|
ELE16-02748
| Electrical Rough-In | 8/29/2016 | 8/29/2016 | 8/29/2016 2:46:27 PM | P | PASS |
|
|
Door code CAM, if you have any questions, please call the lead on the job, Luke at ###-####. Thank you!! Phone #: ###-#### Inspection requested via web by Clay Morgan ri ok bath, kitchen, new bedroom at rear
|
ELE16-02004
| Final | 8/29/2016 | 8/29/2016 | 8/29/2016 2:44:39 PM | P | PASS |
|
|
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk ok final
|
ELE16-02090
| Final | 8/29/2016 | 8/29/2016 | 8/29/2016 2:43:50 PM | P | PASS |
|
|
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk ok final
|
ELE16-02668
| Final | 8/29/2016 | 8/29/2016 | 8/29/2016 2:43:08 PM | P | PASS |
|
|
well house ready to final Phone #: ###-#### Inspection requested via web by Bob Glenn ok final
|
ELE16-02288
| Final | 8/29/2016 | 8/29/2016 | 8/29/2016 1:26:26 PM | P | PASS |
|
|
call prior to arrival for access instructions Phone #: ###-#### Inspection requested via web by Patrick Paz ok final
|
ELE16-00082
| Final | 8/27/2016 | 8/29/2016 | 8/29/2016 12:32:29 PM | A | PART |
|
|
units 121 123 125 127 220 Phone #: ###-#### Inspection requested via web by Tracy Robertson ok as requested
|
ELE16-00080
| Final | 8/27/2016 | 8/29/2016 | 8/29/2016 11:41:18 AM | A | PART |
|
|
units 105 107 109 110 113 115 210 Phone #: ###-#### Inspection requested via web by Tracy Robertson ok as requested
|
ELE16-02775
| Electrical Rough-In | 8/28/2016 | 8/29/2016 | 8/29/2016 9:44:54 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by shane miller called, left correction notice, NEC 314.23 shall not use screws inside box not listed for the purpose, 300.4(A) shall install steel plate if edge of bored hole is less than 1 1/4" fron edge of framing member, 334.30 shall securely fasten nm cabe within 12" of termination, 210.52(E) shall install receptacle at front and rear of dwelling
|
ELE16-02748
| Rough-In Permanent Service | 8/26/2016 | 8/29/2016 | 8/29/2016 8:49:45 AM | A | CANC |
|
|
Door code is CAM, our guys should be there if you have any questions. Luke is the J-man on the job. Thank you! Phone #: ###-#### Inspection requested via web by Clay Morgan see p/s
|
ELE16-02748
| Permanent Service | 8/29/2016 | 8/29/2016 | 8/29/2016 8:41:06 AM | A | PASS |
|
|
Door code is CAM, our guys should be there if you have any questions. Luke is the J-man on the job. Thank you! Phone #: ###-#### Inspection requested via web by Clay Morgan p/s o/h rec ok
|
ELE16-02036
| Final | 8/29/2016 | 8/29/2016 | 8/29/2016 8:38:24 AM | A | PASS |
|
|
access 1234 Phone #: ###-#### Inspection requested via web by David Nelson ok final
|