Inspections for the day of: Monday, August 29, 2016.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02791 ELE-Aging Inspection8/29/20168/29/20168/30/2016 9:44:56 AM CANC
too busy
ELE11-00879 ELE-Aging Inspection8/29/20168/29/20168/30/2016 9:44:35 AM CANC
too busy
ELE16-02358 Electrical Rough-In8/29/20168/29/20168/29/2016 2:29:11 PMPPASS
Need grid inspection, okay to cover grid. Lock Box 1618. Phone #: ###-#### Inspection requested via web by Dean Gernaat
ceilings only ok cover
ELE16-02512 Electrical Rough-In8/29/20168/29/20168/29/2016 2:03:11 PMPPASS
Kevin-underground to cover Phone #: ###-####
underground from solar panels ok cover
ELE16-02805 Rough-In Permanent Service8/29/20168/29/20168/29/2016 1:41:26 PMPPASS
Phone #: ###-#### Inspection requested via web by Eric Brown
rough-in ok cover p/s u/g n ok
ELE16-01378 Final8/26/20168/29/20168/29/2016 1:18:00 PMPPASS
replaced wp outlet Phone #: ###-#### Inspection requested via web by Kevin Koomler
final ok
ELE16-02636 Electrical Rough-In8/26/20168/29/20168/29/2016 1:00:55 PMACANC
Dean Phone #: ###-#### turned into conference
ELE16-02636 Conference8/29/20168/29/20168/29/2016 1:00:42 PMPDONE
Dean Phone #: ###-####
Discussed wiring methods to get job done safely.
Dean was advised that he would have be the soul owner and shall live in this property for 2 years before selling the property, also warned his friend that he shall not help with the wiring due to State statue will not allow friends to help, only family members.
ELE16-01062 Electrical Rough-In8/25/20168/29/20168/29/2016 9:50:18 AMADONE
We are requesting a rough-in inspection for Monday August 29th in the morning. Our onsite contact is Rich @ ###-####. Thank you,
Phone #: ###-#### Inspection requested via web by Clint Tate
Verified Ground Fault performance testing. Will still have to run generator once all parts arrive.
ELE16-02793 Permanent Service8/27/20168/29/20168/29/2016 9:22:41 AMAPASS
Check in at the front office, ask for Josh or Mike and they will show you the work site. If you have any questions please call Dan at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell
Will need t verify k/o seal in bottom of disconnect
p/s u/g rec ok
ELE16-02615 Final8/29/20168/29/20168/29/2016 8:51:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Patrick Paz
upstairs bath final ok
ELE16-01772 Final8/26/20168/29/20168/29/2016 8:28:41 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
406.5 receptacles shall be rigidly held in place
200.10 reverse polarity in master bed
250.94 utility bonding system required
422.30 lockout for ovens
garage GFCI in-op can not check w/p's