Inspections for the day of: Monday, August 29, 2016.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-04407 FIRE-Final Inspection8/25/20168/29/20168/29/2016 3:24:53 PMACANC
Looking to schedule Life Safety Inspection. The sprinkler contractor will meet on site. Fidel-###-####

Plans are in Managers office. Phone #: ###-#### Inspection requested via web by jason epperson
FIR16-00479 INSP-Final Inspection8/29/20168/29/20168/29/2016 3:23:57 PMPPASS
Permit finaled
FIR16-00530 INSP-Sprinkler Rough-in8/29/20168/29/20168/29/2016 3:23:35 PMPPASS
Rough-in passed. Piping is ok to cover
BLD16-02633 FIRE-Final Inspection8/26/20168/29/20168/29/2016 10:21:32 AMAFAIL
Provide annual inspection for both fire extinguisheres, remove deadbolt from the west exit door, provide sticker at the east exit door.
BLD16-02550 FIRE-Final Inspection8/26/20168/29/20168/29/2016 10:08:24 AMAFAIL
Repair or remove the two non-functional exit signs and remove the non-functional door mag at the west exit.
BLD16-02435 FIRE-Final Inspection8/26/20168/29/20168/29/2016 10:07:45 AMAPASS
Life safety passed. Contractor to provide a permanant suite number prior to a building inspeciton.
BLD16-03131 FIRE-Final Inspection8/26/20168/29/20168/29/2016 10:06:52 AMAPASS
Life safety passed. Owner to remove the thumbturn dead bolt prior to a building inspection.