Inspections for the day of: Thursday, August 29, 2019.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-03766 Final8/28/20198/29/20198/29/2019 3:57:32 PMPPASS
Please call home owner Diana when in route to home ###-#### Phone #: ###-#### Inspection requested via web by Carolyn Rudd
- furnace ac coil co ok
MEC19-03758 Final8/26/20198/29/20198/29/2019 2:21:33 PMPFAIL
INSTALLER GERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- new RTU needs smoke detection shut down installed either using smoke detectors installed in return duct or using building fire alarm system to shut down RTU
MEC19-03758 Pressure Test8/26/20198/29/20198/29/2019 2:19:27 PMPPASS
INSTALLER GERRY ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
- 60lb gas pressure test ok to new RTU
MEC19-03885 Final8/29/20198/29/20198/29/2019 1:40:00 PMPFAIL
Phone #: ###-#### Inspection requested via web by Brandon Sorensen
- no access to suite and will need a ladder to access the equipment on the roof. Reschedule inspection with bank
MEC19-03768 Pressure Test8/28/20198/29/20198/29/2019 1:28:41 PMPPASS
Phone #: ###-#### Inspection requested via web by Frank Marturello
- 5lb flue pressure test ok
MEC19-03768 Rough-in8/28/20198/29/20198/29/2019 1:28:28 PMPPASS
Phone #: ###-#### Inspection requested via web by Frank Marturello
- R/I ok
MEC19-03874 Final8/28/20198/29/20198/29/2019 11:41:55 AMAPASS
call Mary before coming Phone #: ###-#### Inspection requested via web by Kim Lithander
- furnace ac coil co ok
MEC19-00174 Final8/28/20198/29/20198/29/2019 11:13:35 AMANH
Phone #: ###-#### Inspection requested via web by Denise Colin
- no access to home
- looks like house is vacant left notice on front door
MEC19-03678 Rough-in8/28/20198/29/20198/29/2019 11:02:37 AMAPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves
- R/I ok
- I also tagged location with a mech do not cover sticker. Need to see fireplace permit R/I still by others
MEC19-03678 Pressure Test8/28/20198/29/20198/29/2019 10:57:01 AMAPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves
- 5lb flue pressure test ok
- 20lb gas pressure test ok
- tagged meter location
MEC19-01222 Final8/28/20198/29/20198/29/2019 10:24:36 AMAFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak
- A/C's need leveled
- outside air grilles need fixed on back side of building
- dryer vent stickers need installed through out building
MEC19-03522 Final8/28/20198/29/20198/29/2019 9:37:43 AMANR
Please contact Jasper for access. We will be on site at 9:30 AM. Phone #: ###-#### Inspection requested via web by Ted Dumont
- not ready and 5lb flue has a leak
MEC19-03684 Final8/28/20198/29/20198/29/2019 9:14:53 AMAFAIL
Matt Phone #: ###-####
- A/C line set needs UV protection
- need to see an electrical permit issued for the A/C relocation
- need to add gas pressure test, and exhaust fan to permit
MEC19-03684 Pressure Test8/28/20198/29/20198/29/2019 9:05:51 AMAPASS
Call ahead // Matt Phone #: ###-####
- 20lb gas pressure test ok
- tagged meter location
- need to add gas pressure test to permit
MEC19-00216 Final8/27/20198/29/20198/29/2019 8:34:34 AMAFAIL
If you would call me first so I can make sure the building is unlocked. Thanks. Phone #: ###-#### Inspection requested via web by Doug Turner
- no access to inspection mini split system on roof and inside office
MEC18-01748 Mec-Aging Inspection8/29/20198/29/20198/29/2019 8:06:49 AM PASS
Doc Permit Expired ok not active
MEC18-01748 DOC - Permit Expired8/29/20198/29/20198/29/2019 8:06:31 AMAPASS
Doc Permit Expired ok not active