ELE04-01317
| Final | 7/29/2004 | 8/3/2004 | 8/3/2004 9:43:38 AM | P | CANC |
|
|
Call ###-#### for Mr. Miller to meet you between 12:00-2:00.; Phone #: ###-#### Internet Inspection Request from: Dana Moyer Inspection cancelled from web by: Dana Moyer
|
ELE04-02068
| Electrical Rough-In | 8/2/2004 | 8/3/2004 | 8/3/2004 12:00:00 AM | A | FAIL |
|
|
HARVEY - CEILING; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
314.23 Supports.
Enclosures within the scope of this article shall be supported in accordance with one or more of the provisions in 314.23(A) through (H).
300.11 Securing and Supporting.
(A) Secured in Place. Raceways, cable assemblies, boxes, cabinets, and fittings shall be securely fastened in place.
300.15 Boxes, Conduit Bodies, or Fittings - Where Required.
Where the wiring method is conduit, tubing, Type AC cable, Type MC cable, Type MI cable, nonmetallic-sheathed cable, or other cables, a box or conduit body complying with Article 314 shall be installed at each conductor splice point, outlet point, switch point, junction point, termination point, or pull point, unless otherwise permitted in 300.15(A) through (M).
8/3/2004 9:17:25 AM
|
ELE04-02275
| Final | 8/2/2004 | 8/3/2004 | 8/3/2004 12:00:00 AM | A | NR |
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
|
ELE04-01481
| Electrical Rough-In | 8/2/2004 | 8/3/2004 | 8/3/2004 12:00:00 AM | A | PASS |
|
|
bob; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
P/S O/H N Ok
R/I Ok 8/3/2004 9:33:44 AM
|
ELE04-02275
| Electrical Rough-In | 8/3/2004 | 8/3/2004 | 8/3/2004 12:00:00 AM | A | PASS |
|
|
|
ELE04-02120
| Final | 7/29/2004 | 8/3/2004 | 8/3/2004 12:00:00 AM | A | PASS |
|
|
kevin; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
ELE04-02236
| Final | 8/3/2004 | 8/3/2004 | 8/3/2004 12:00:00 AM | P | NR |
|
|
Permanent Service Inspection ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
P/S O/H R Ok 8/3/2004 12:26:08 PM
|
ELE04-02301
| Conference | 8/3/2004 | 8/3/2004 | 8/3/2004 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 8/3/2004 at 7:36:31 AM. Contact: ###-####. please call for access
talked about the 50% rule 8/3/2004 3:31:19 PM
|
ELE04-02290
| Permanent Service | 8/3/2004 | 8/3/2004 | 8/3/2004 12:00:00 AM | P | PASS |
|
|
Alan; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
P/S U/g N Ok 8/3/2004 10:29:22 AM
|
ELE04-01729
| Final | 8/3/2004 | 8/3/2004 | 8/3/2004 12:00:00 AM | P | PASS |
|
|
dave; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
ELE04-02331
| Electrical Rough-In | 8/3/2004 | 8/3/2004 | 8/3/2004 12:00:00 AM | P | PART |
|
|
###-#### - bob
u/g ok 8/3/2004 2:54:09 PM
|
ELE04-02332
| Electrical Rough-In | 8/3/2004 | 8/3/2004 | 8/3/2004 12:00:00 AM | P | PART |
|
|
###-#### - bob
U/G Ok 8/3/2004 4:21:24 PM
|
ELE04-02335
| Rough-In Permanent Service | 8/3/2004 | 8/3/2004 | 8/3/2004 12:00:00 AM | P | FAIL |
|
|
###-#### dennis
service not grounded properly
258.148 several locations
one box 2gang upstairs over filled
210.52 upstairs by handrail
8/3/2004 1:51:56 PM
|