Inspections for the day of: Wednesday, August 3, 2005.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01561 ELE-Aging Inspection8/3/20058/3/20058/4/2005 8:59:42 AM PEND
WSUC waiting for contractor to call for inspection
ELE04-02672 Final8/2/20058/3/20058/3/2005 5:12:16 PMPFAIL
Please call Gary 30 minutes in advance at ###-####; Phone #: ###-#### Internet Inspection Request from: Gary Gettman recept and lights in din rm cabinet have no power, and class 2 circuit , and xformer ,control device in same box as high voltage system shall meet requirements of 725.54,55 called
ELE05-02795 Electrical Rough-In8/3/20058/3/20058/3/2005 4:25:58 PMPFAIL
paul; Phone #: ###-#### Internet Inspection Request from: Barbara Moore needs to find out if building is all one to is shop out back seperate from house it is tied too the house with a roof, 312.5(C) pvc shall exit top of panel and meet exception requirements
ELE05-00732 Final8/3/20058/3/20058/3/2005 3:46:26 PMPNR
please call 45 min prior to meet///richard; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa needs to finish fire alarm , note needs proper rated low voltage wire where mixed with high , bushings or connectors where cables enter boxes, shall provide hole back of fixture to access box surface mounted strips in basement met contractor at job site
ELE05-01977 Final8/3/20058/3/20058/3/2005 2:33:43 PMPPASS
matt; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok card signed
ELE05-02817 Rough-In Permanent Service8/3/20058/3/20058/3/2005 1:49:28 PMPPASS
brian; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa no r/i
p/s u/g rec. ok
ELE05-02719 Temporary Service8/3/20058/3/20058/3/2005 1:45:32 PMPPASS
troy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/s u/g new ok
ELE05-02481 Temporary Service8/3/20058/3/20058/3/2005 1:45:06 PMPPASS
troy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/s u/g new ok
ELE05-02805 Rough-In Permanent Service8/3/20058/3/20058/3/2005 1:09:56 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Joe Thomas notice posted shall provide plans at job site, r/i ok
p/s u/g new ok
ELE05-02800 Electrical Rough-In8/3/20058/3/20058/3/2005 12:14:40 PMAFAIL
Scheduled by a contractor via Hello! on 8/3/2005 at 6:17:37 AM. Contact: ###-####. 300.4, 314.16, 300.14, 334.30, 314,17(C) sheath shall extend 1/4 into box, complete all makeup and install boxes in bath rm
ELE05-02333 Final8/2/20058/3/20058/3/2005 11:00:14 AMAPASS
Internet Inspection Request from: Radon Elaina final for sign only
ELE05-02805 Final8/2/20058/3/20058/3/2005 10:17:58 AMAFAIL
Please contact Heath ###-#### with any questions; Phone #: ###-#### Internet Inspection Request from: Joe Thomas not ready for final called
ELE04-03054 Electrical Rough-In8/2/20058/3/20058/3/2005 9:50:51 AMAPART
Rough-in inspection for exterior recessed lighting; Phone #: ###-#### Internet Inspection Request from: Barry Kendall r/i ok anop
ELE05-02709 Final8/2/20058/3/20058/3/2005 9:16:24 AMAFAIL
Final ( NH on 7/29/); Phone #: ###-#### Internet Inspection Request from: Cathy Felin 110.3(B)manufactures instructions no load conductors shall exit top of p/s,250.104(A)(1) bond water with #4, 344.46 bushings for rigid nipples, 110.12(A) seal unused KOs, 250.92(A)(3) choke GEC both ends, or remove emt raceway
ELE05-02804 Final8/3/20058/3/20058/3/2005 8:31:43 AMAPASS
ELE05-02804 Permanent Service8/2/20058/3/20058/3/2005 8:31:30 AMAPASS
Please contact Doug at ###-#### or ###-#### to gain access to location.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH p/s o/h rec. ok
ELE05-02801 Temporary Service8/2/20058/3/20058/3/2005 8:03:22 AMAPASS
overhead service; Phone #: ###-#### Internet Inspection Request from: dennis mcneely t/s o/h new ok
ELE05-02817 Temporary Service8/3/20058/3/20058/3/2005 12:00:00 AMPCANC
repaired feeder to panel in detacthed garage for temp. power; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH