ELE05-01561
| ELE-Aging Inspection | 8/3/2005 | 8/3/2005 | 8/4/2005 8:59:42 AM | | PEND |
|
|
WSUC waiting for contractor to call for inspection
|
ELE04-02672
| Final | 8/2/2005 | 8/3/2005 | 8/3/2005 5:12:16 PM | P | FAIL |
|
|
Please call Gary 30 minutes in advance at ###-####; Phone #: ###-#### Internet Inspection Request from: Gary Gettman recept and lights in din rm cabinet have no power, and class 2 circuit , and xformer ,control device in same box as high voltage system shall meet requirements of 725.54,55 called
|
ELE05-02795
| Electrical Rough-In | 8/3/2005 | 8/3/2005 | 8/3/2005 4:25:58 PM | P | FAIL |
|
|
paul; Phone #: ###-#### Internet Inspection Request from: Barbara Moore needs to find out if building is all one to is shop out back seperate from house it is tied too the house with a roof, 312.5(C) pvc shall exit top of panel and meet exception requirements
|
ELE05-00732
| Final | 8/3/2005 | 8/3/2005 | 8/3/2005 3:46:26 PM | P | NR |
|
|
please call 45 min prior to meet///richard; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa needs to finish fire alarm , note needs proper rated low voltage wire where mixed with high , bushings or connectors where cables enter boxes, shall provide hole back of fixture to access box surface mounted strips in basement met contractor at job site
|
ELE05-01977
| Final | 8/3/2005 | 8/3/2005 | 8/3/2005 2:33:43 PM | P | PASS |
|
|
matt; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok card signed
|
ELE05-02817
| Rough-In Permanent Service | 8/3/2005 | 8/3/2005 | 8/3/2005 1:49:28 PM | P | PASS |
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa no r/i p/s u/g rec. ok
|
ELE05-02719
| Temporary Service | 8/3/2005 | 8/3/2005 | 8/3/2005 1:45:32 PM | P | PASS |
|
|
troy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/s u/g new ok
|
ELE05-02481
| Temporary Service | 8/3/2005 | 8/3/2005 | 8/3/2005 1:45:06 PM | P | PASS |
|
|
troy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/s u/g new ok
|
ELE05-02805
| Rough-In Permanent Service | 8/3/2005 | 8/3/2005 | 8/3/2005 1:09:56 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas notice posted shall provide plans at job site, r/i ok p/s u/g new ok
|
ELE05-02800
| Electrical Rough-In | 8/3/2005 | 8/3/2005 | 8/3/2005 12:14:40 PM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/3/2005 at 6:17:37 AM. Contact: ###-####. 300.4, 314.16, 300.14, 334.30, 314,17(C) sheath shall extend 1/4 into box, complete all makeup and install boxes in bath rm
|
ELE05-02333
| Final | 8/2/2005 | 8/3/2005 | 8/3/2005 11:00:14 AM | A | PASS |
|
|
Internet Inspection Request from: Radon Elaina final for sign only
|
ELE05-02805
| Final | 8/2/2005 | 8/3/2005 | 8/3/2005 10:17:58 AM | A | FAIL |
|
|
Please contact Heath ###-#### with any questions; Phone #: ###-#### Internet Inspection Request from: Joe Thomas not ready for final called
|
ELE04-03054
| Electrical Rough-In | 8/2/2005 | 8/3/2005 | 8/3/2005 9:50:51 AM | A | PART |
|
|
Rough-in inspection for exterior recessed lighting; Phone #: ###-#### Internet Inspection Request from: Barry Kendall r/i ok anop
|
ELE05-02709
| Final | 8/2/2005 | 8/3/2005 | 8/3/2005 9:16:24 AM | A | FAIL |
|
|
Final ( NH on 7/29/); Phone #: ###-#### Internet Inspection Request from: Cathy Felin 110.3(B)manufactures instructions no load conductors shall exit top of p/s,250.104(A)(1) bond water with #4, 344.46 bushings for rigid nipples, 110.12(A) seal unused KOs, 250.92(A)(3) choke GEC both ends, or remove emt raceway
|
ELE05-02804
| Final | 8/3/2005 | 8/3/2005 | 8/3/2005 8:31:43 AM | A | PASS |
|
|
|
ELE05-02804
| Permanent Service | 8/2/2005 | 8/3/2005 | 8/3/2005 8:31:30 AM | A | PASS |
|
|
Please contact Doug at ###-#### or ###-#### to gain access to location.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH p/s o/h rec. ok
|
ELE05-02801
| Temporary Service | 8/2/2005 | 8/3/2005 | 8/3/2005 8:03:22 AM | A | PASS |
|
|
overhead service; Phone #: ###-#### Internet Inspection Request from: dennis mcneely t/s o/h new ok
|
ELE05-02817
| Temporary Service | 8/3/2005 | 8/3/2005 | 8/3/2005 12:00:00 AM | P | CANC |
|
|
repaired feeder to panel in detacthed garage for temp. power; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
|