FIR05-00310
| INSP-Final Inspection | 8/2/2005 | 8/3/2005 | 8/3/2005 4:27:25 PM | P | NR |
|
|
Two separate rooms are not complete, alarm notification devices within these areas have not been installed in their final locations.
|
FIR05-00209
| INSP-Sprinkler Rough-in/Hydro | 8/3/2005 | 8/3/2005 | 8/3/2005 3:54:57 PM | P | PART |
|
|
Overhead rough-in is acceptable to cover.
|
FIR05-00429
| INSP-Sprinkler Rough-in | 8/2/2005 | 8/3/2005 | 8/3/2005 3:53:43 PM | P | PART |
|
|
Need to add one upright head in area overspaced at southeast corner, need to verify 3" main connection and EQ brace at last piece of main when installed, all remaining areas are good for cover.
|
FIR05-00190
| INSP-Sprinkler Rough-in/Hydro | 8/3/2005 | 8/3/2005 | 8/3/2005 2:26:08 PM | P | FAIL |
|
|
One hanger is missing on an arm over for the pendent head in the H/K closet. Three other hard lid areas as marked on the approved plans are okay to cover.
|
FIR04-00701
| INSP-Final Inspection | 8/2/2005 | 8/3/2005 | 8/3/2005 2:20:36 PM | P | PASS |
|
|
Fire alarm passed inspection.
|
BLD04-02151
| FIRE-Final Inspection | 8/3/2005 | 8/3/2005 | 8/3/2005 1:14:45 PM | P | PASS |
|
|
Life safety passed inspection.
|
FIR05-00431
| INSP-Sprinkler Rough-in | 8/3/2005 | 8/3/2005 | 8/3/2005 12:50:59 PM | P | PART |
|
|
Overhead rough-in for fire sprinkler is good for cover except one location at a pendent head near a column in the open area to which the arm over has been supported by a ceiling grid wire from the deck, the pipe shall have an approved and listed hanger installed prior to final.
|
BLD04-00944
| FIRE-Conference | 8/2/2005 | 8/3/2005 | 8/3/2005 10:51:43 AM | A | DONE |
|
|
On site conversation with Jim Williams regarding additional exit signage requirements at the stairway exit discharge.
|
MIS05-00105
| FIR-Final | 8/2/2005 | 8/3/2005 | 8/3/2005 9:56:44 AM | A | PASS |
|
|
Life safety finaled.
|