Inspections for the day of: Wednesday, August 3, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00310 INSP-Final Inspection8/2/20058/3/20058/3/2005 4:27:25 PMPNR
Two separate rooms are not complete, alarm notification devices within these areas have not been installed in their final locations.
FIR05-00209 INSP-Sprinkler Rough-in/Hydro8/3/20058/3/20058/3/2005 3:54:57 PMPPART
Overhead rough-in is acceptable to cover.
FIR05-00429 INSP-Sprinkler Rough-in8/2/20058/3/20058/3/2005 3:53:43 PMPPART
Need to add one upright head in area overspaced at southeast corner, need to verify 3" main connection and EQ brace at last piece of main when installed, all remaining areas are good for cover.
FIR05-00190 INSP-Sprinkler Rough-in/Hydro8/3/20058/3/20058/3/2005 2:26:08 PMPFAIL
One hanger is missing on an arm over for the pendent head in the H/K closet. Three other hard lid areas as marked on the approved plans are okay to cover.
FIR04-00701 INSP-Final Inspection8/2/20058/3/20058/3/2005 2:20:36 PMPPASS
Fire alarm passed inspection.
BLD04-02151 FIRE-Final Inspection8/3/20058/3/20058/3/2005 1:14:45 PMPPASS
Life safety passed inspection.
FIR05-00431 INSP-Sprinkler Rough-in8/3/20058/3/20058/3/2005 12:50:59 PMPPART
Overhead rough-in for fire sprinkler is good for cover except one location at a pendent head near a column in the open area to which the arm over has been supported by a ceiling grid wire from the deck, the pipe shall have an approved and listed hanger installed prior to final.
BLD04-00944 FIRE-Conference8/2/20058/3/20058/3/2005 10:51:43 AMADONE
On site conversation with Jim Williams regarding additional exit signage requirements at the stairway exit discharge.
MIS05-00105 FIR-Final8/2/20058/3/20058/3/2005 9:56:44 AMAPASS
Life safety finaled.