Inspections for the day of: Thursday, August 3, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-02298 Permanent Service8/3/20068/3/20068/3/2006 4:26:34 PMPFAIL
###-#### - marv 250.52(A)(1)or104(A)(1) grd or bond water sized too T250.66, #2 cu 250.90,92 use bond bushing not bonding locknut, where concentrics are encountered, 250.64(E) use listed or plastic fitting for GEC not 3/8 romex conn., 314.28 j box above service disconnects shall be of large enough size for straight pulls, 312.5(C) exception pvc tob of jbox shall meet rquirements of code noted terminate service wirs to far right panel to main breaker not main lugs use backfed device cow
ELE06-00073 Final8/2/20068/3/20068/3/2006 3:00:20 PMPPASS
virgil ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
ok no card
ELE06-02767 Electrical Rough-In8/3/20068/3/20068/3/2006 2:23:05 PMPPART
Cover for panel wall; Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok
ELE04-01830 Final8/2/20068/3/20068/3/2006 1:27:12 PMPNR
please call prior to inspection so it can be opened ###-#### Mike see added r/i
ELE04-01830 Electrical Rough-In8/3/20068/3/20068/3/2006 1:26:48 PMPPART
please call prior to inspection so it can be opened ###-#### Mike ok corr. made, bath rm ok, island in kit needs too meet requirements of 210.52 (C)(1) 2ft 4ft rule gave cover contractor will corr. I will check it at time of final
ELE06-02827 Permanent Service8/2/20068/3/20068/3/2006 12:12:58 PMPPASS
SCOTT; Phone #: ###-#### Internet Inspection Request from: Sean DeLacyh
p/s o/h rec. ok
ELE06-02827 Final8/3/20068/3/20068/3/2006 12:12:12 PMAPASS
SCOTT; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok
ELE06-02196 Final8/2/20068/3/20068/3/2006 9:44:03 AMAPASS
pat; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
ELE06-02853 Electrical Rough-In8/2/20068/3/20068/3/2006 9:09:39 AMAPASS
ron; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles walls and ceilings
ELE06-02860 Final8/2/20068/3/20068/3/2006 8:30:04 AMAPASS
This is Unit "H". We wired a new 120 volt receptacle for gas range to plug into and fed it from the existing counter top receptacle to the right of the
range.(6070781w)Tech/Dan/###-####. Thanks!!!!; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok
ELE06-01128 Final8/2/20068/3/20068/3/2006 7:54:58 AMACANC
code ###-####; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
ELE06-01127 Final8/2/20068/3/20068/3/2006 7:54:29 AMACANC
code ###-####; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
ELE06-01129 Final8/3/20068/3/20068/3/2006 7:53:57 AMACANC
code ###-####; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
ELE06-00896 Final8/3/20068/3/20068/3/2006 7:52:58 AMACANC
code ###-####; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
ELE06-00895 Final8/3/20068/3/20068/3/2006 7:52:42 AMACANC
code ###-####; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson