ELE05-01394
| Electrical Rough-In | 8/3/2006 | 8/3/2006 | 8/3/2006 4:15:57 PM | P | PASS |
|
|
Note: anytim after 1:00 please; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles told owner to add 1 recpt upstairs room with chimney, ric ok
|
ELE06-02704
| Electrical Rough-In | 8/2/2006 | 8/3/2006 | 8/3/2006 3:16:03 PM | P | PART |
|
|
Please inspect the under slab conduit in the C-wing.; Phone #: ###-#### Internet Inspection Request from: Jim Friend n wing c u/g ok to cover
|
ELE06-02847
| Temporary Service | 8/2/2006 | 8/3/2006 | 8/3/2006 1:37:07 PM | P | PASS |
|
|
daryl; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley t/s o/h n ok
|
ELE06-02502
| Electrical Rough-In | 8/2/2006 | 8/3/2006 | 8/3/2006 11:48:13 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 8/2/2006 at 1:02:40 PM. Contact: ###-####. ric ok, contr says no x-ray equip per bldr and others
|
ELE06-02855
| Permanent Service | 8/2/2006 | 8/3/2006 | 8/3/2006 10:30:43 AM | A | FAIL |
|
|
This is for Idaho Power to reconnect the meter. Id.Power request a sticker on it before they can put power to it. My cell number is ###-####. Thanks Randy; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher called contr, left corr notice, 334.12(B) nm cable shall not be used where exposed to excessive dampness, 312.5 all conductors entering enclosure shall have abrasion protection, 358.30,352.30 raceways shall be strapped within 3' of box,300.18 raceways shall be installed as a complete system, including locknuts,210.8(A)(3) outside recpt shall be gfci,406.8(B) w/p cover shall be on recpt outside, 408.4 circuit directory shall be complete,230.24(B) drip loop shall be min 10' above grade, 110.14(A) connection of conductors shall be by pressure connectors or lugs, 250 all grounding shall be brought up to code
|
ELE06-01919
| Final | 8/2/2006 | 8/3/2006 | 8/3/2006 9:37:36 AM | A | FAIL |
|
|
jeff- call prior to insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley told owner, left corr notice, nec 408.4 complete and definitive circuit directory shall be provided in panels and identify smoke detector circuit, 210.12(B) arc-fault circuit interruptor shall be installed for bedroom, 110.3 panelboard deadfront screw shall be installed,230.28 service mast shall have guy kit installed
|
ELE06-00113
| Electrical Rough-In | 8/2/2006 | 8/3/2006 | 8/3/2006 8:55:06 AM | A | PART |
|
|
CEIKING INSPECTION - LOBBY AREA. CONTACT: GREG PACK; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ceilings ok to cover anop
|
ELE06-02846
| Temporary Service | 8/2/2006 | 8/3/2006 | 8/3/2006 12:00:00 AM | P | CANC |
|
|
per daryl; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
|
ELE06-02845
| Temporary Service | 8/2/2006 | 8/3/2006 | 8/3/2006 12:00:00 AM | P | CANC |
|
|
per daryl; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
|