ELE07-01473
| Electrical Rough-In | 8/3/2007 | 8/3/2007 | 8/3/2007 4:09:19 PM | P | PART |
|
|
chris - uffer Phone #: ###-#### ok for concrete cover
|
ELE07-02723
| Electrical Rough-In | 8/3/2007 | 8/3/2007 | 8/3/2007 3:20:54 PM | P | PART |
|
|
dan - cover Phone #: ###-#### walls ok
|
ELE07-02711
| Electrical Rough-In | 8/3/2007 | 8/3/2007 | 8/3/2007 2:36:08 PM | P | NR |
|
|
dennis Phone #: ###-#### called all new wire shall be mc/ac cable or raceway for comm. work and shall meet NEC requirerments for non dwelling conference ok only
|
ELE07-02685
| Permanent Service | 8/3/2007 | 8/3/2007 | 8/3/2007 1:45:29 PM | P | PASS |
|
|
gene - re-inspection Phone #: ###-#### p/s u/g new ok
|
ELE07-02685
| Final | 8/3/2007 | 8/3/2007 | 8/3/2007 1:44:59 PM | P | PASS |
|
|
gene - re-inspection Phone #: ###-####
|
ELE07-02725
| Final | 8/3/2007 | 8/3/2007 | 8/3/2007 12:51:06 PM | P | CANC |
|
|
james Phone #: ###-#### called
|
ELE07-02725
| Electrical Rough-In | 8/3/2007 | 8/3/2007 | 8/3/2007 12:50:35 PM | P | NR |
|
|
james Phone #: ###-#### support jboxes, bond steel to service, no violations retained remove wiring in violation of NEC (owner wired pump) called
|
ELE07-02648
| Permanent Service | 8/3/2007 | 8/3/2007 | 8/3/2007 12:22:13 PM | P | CANC |
|
|
tilda Phone #: ###-#### see added DOC final owner secured contractor to take over job abd correct violations
|
ELE07-02648
| DOC - Permit Finaled | 8/3/2007 | 8/3/2007 | 8/3/2007 12:21:09 PM | P | DONE |
|
|
tilda Phone #: ###-#### owner secured contractor to take over job and correct violations
|
ELE07-01322
| Final | 8/2/2007 | 8/3/2007 | 8/3/2007 10:44:18 AM | A | NR |
|
|
Phone #: ###-#### Internet Inspection Request from: Gary Foreman called
|
ELE07-02648
| Permanent Service | 8/2/2007 | 8/3/2007 | 8/3/2007 10:23:32 AM | A | FAIL |
|
|
P\S only Phone #: ###-#### corr. posted met owner 250.148(C) grd jbox sized to table 250.122
|
ELE07-02503
| Electrical Rough-In | 8/2/2007 | 8/3/2007 | 8/3/2007 9:45:23 AM | A | PART |
|
|
don ceiling cover upstairs Note: please call 1/2 hr prior to inspection Phone #: ###-#### 2nd floor hall ceiling and conference about service
|
ELE07-02685
| Permanent Service | 8/2/2007 | 8/3/2007 | 8/3/2007 8:40:17 AM | A | FAIL |
|
|
gene Phone #: ###-#### corr called left message 250.92(A)(3) bond both end of emt for GEC, 110.14 wirenut not listed for cual, 110.3(B) switch shall use manufactures listed grd bar kit for suzi rating, 250.24 shall terminate GEC to grounded conductor at service, shall not use telephone L fitting for electrical wiring
|
ELE07-00258
| Final | 8/2/2007 | 8/3/2007 | 8/3/2007 12:00:00 AM | A | CANC |
|
|
rick Note: if possible 8:00 am please call Phone #: ###-####
|