Inspections for the day of: Friday, August 3, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01473 Electrical Rough-In8/3/20078/3/20078/3/2007 4:09:19 PMPPART
chris - uffer Phone #: ###-#### ok for concrete cover
ELE07-02723 Electrical Rough-In8/3/20078/3/20078/3/2007 3:20:54 PMPPART
dan - cover Phone #: ###-#### walls ok
ELE07-02711 Electrical Rough-In8/3/20078/3/20078/3/2007 2:36:08 PMPNR
dennis Phone #: ###-#### called all new wire shall be mc/ac cable or raceway for comm. work and shall meet NEC requirerments for non dwelling conference ok only
ELE07-02685 Permanent Service8/3/20078/3/20078/3/2007 1:45:29 PMPPASS
gene - re-inspection Phone #: ###-####
p/s u/g new ok
ELE07-02685 Final8/3/20078/3/20078/3/2007 1:44:59 PMPPASS
gene - re-inspection Phone #: ###-####
ELE07-02725 Final8/3/20078/3/20078/3/2007 12:51:06 PMPCANC
james Phone #: ###-#### called
ELE07-02725 Electrical Rough-In8/3/20078/3/20078/3/2007 12:50:35 PMPNR
james Phone #: ###-#### support jboxes, bond steel to service, no violations retained remove wiring in violation of NEC (owner wired pump) called
ELE07-02648 Permanent Service8/3/20078/3/20078/3/2007 12:22:13 PMPCANC
tilda Phone #: ###-#### see added DOC final owner secured contractor to take over job abd correct violations
ELE07-02648 DOC - Permit Finaled8/3/20078/3/20078/3/2007 12:21:09 PMPDONE
tilda Phone #: ###-#### owner secured contractor to take over job and correct violations
ELE07-01322 Final8/2/20078/3/20078/3/2007 10:44:18 AMANR
Phone #: ###-#### Internet Inspection Request from: Gary Foreman called
ELE07-02648 Permanent Service8/2/20078/3/20078/3/2007 10:23:32 AMAFAIL
P\S only Phone #: ###-#### corr. posted met owner 250.148(C) grd jbox sized to table 250.122
ELE07-02503 Electrical Rough-In8/2/20078/3/20078/3/2007 9:45:23 AMAPART
don ceiling cover upstairs Note: please call 1/2 hr prior to inspection Phone #: ###-####
2nd floor hall ceiling and conference about service
ELE07-02685 Permanent Service8/2/20078/3/20078/3/2007 8:40:17 AMAFAIL
gene Phone #: ###-#### corr called left message 250.92(A)(3) bond both end of emt for GEC, 110.14 wirenut not listed for cual, 110.3(B) switch shall use manufactures listed grd bar kit for suzi rating, 250.24 shall terminate GEC to grounded conductor at service, shall not use telephone L fitting for electrical wiring
ELE07-00258 Final8/2/20078/3/20078/3/2007 12:00:00 AMACANC
rick Note: if possible 8:00 am please call Phone #: ###-####