Inspections for the day of: Friday, August 3, 2007.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01625 ELE-Aging Inspection8/3/20078/3/20078/8/2007 9:22:39 AM DONE
see final
ELE07-01535 Final8/3/20078/3/20078/3/2007 3:56:07 PMPPASS
looked at sign, ok to final
ELE07-01397 Final8/3/20078/3/20078/3/2007 3:54:35 PMPPASS
looked at sign, ok to final
ELE07-02653 Rough-In Permanent Service8/3/20078/3/20078/3/2007 3:50:50 PMPPASS
permanent service and trench Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ric ok, u/g ok to cover, p/s u/g n ok
ELE06-03959 Final8/2/20078/3/20078/3/2007 2:59:29 PMPPASS
matt Phone #: ###-#### ok to final, signed struct card, reviewed with elect about getting permit for 2nd floor x-ray machine
ELE07-02720 Permanent Service8/2/20078/3/20078/3/2007 1:55:07 PMPPASS
todd Note: early afternoon please Phone #: ###-#### p/s u/g rec ok
ELE07-02671 Final8/2/20078/3/20078/3/2007 1:41:09 PMPPASS
Service change. Will call inspector when I am about an hour from completion. Thank you! Phone #: ###-#### Internet Inspection Request from: Adam Staigle p/s o/h rec ok
ELE07-01359 Final8/3/20078/3/20078/3/2007 1:25:08 PMPPASS
Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok to final, signed occ card
ELE07-02709 Electrical Rough-In8/2/20078/3/20078/3/2007 12:33:43 PMPFAIL
call for answers (not much to inspect)thanks Brad Phone #: ###-#### Internet Inspection Request from: Brad Baker called, left message, left corr notice, nec 300.11 tie wires required for all fixtures, 330.30(B) &348.30(A) mc and fmc shall be secured within 12" of term point, 300.11(A) cables shall not be supported by grid, 725.3(B) lv cables that are abandoned shall be removed, BCC no violations shall be retained, blank off recpt in ceiling cavity
ELE07-02716 Rough-In Permanent Service8/2/20078/3/20078/3/2007 11:45:56 AMAPASS
brandon ###-#### ric ok, p/s u/g n ok
ELE07-02715 Final8/2/20078/3/20078/3/2007 10:29:56 AMAPASS
Pat; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
ELE07-02473 Electrical Rough-In8/3/20078/3/20078/3/2007 10:05:33 AMPPASS
We failed the trench inspection for the entryway. This is a reinspect. Thank You Phone #: ###-#### Internet Inspection Request from: Craig Korell correction made, ok to cover u/g in parking lot
ELE07-02350 Final8/2/20078/3/20078/3/2007 9:37:33 AMAPASS
Call for key location Phone #: ###-#### Internet Inspection Request from: Terrie Dickson called to chg label on breakers, ok to final
ELE07-02706 Electrical Rough-In8/2/20078/3/20078/3/2007 9:10:27 AMAFAIL
###-#### Internet Inspection Request from: Todd Holbrook called, left message, left corr notice, nec 300.4(A)&(D) edge of bored holes and raceways shall be 1/14" from edge of framing members, 330.30(B) mc cable shall be secured within 12" of term point, 110.26(F)(1) there shall be no foreign systems in dedicated electrical space over panel, 300.5 u/g shall be covered with minimum 2" concrete
ELE07-02688 Permanent Service8/2/20078/3/20078/3/2007 8:18:21 AMAPASS
Permanant Service please call AJ with any questions ###-#### Phone #: ###-#### Internet Inspection Request from: todd hall p/s, exst meter pak, n, ok, meter A
ELE07-02285 Electrical Rough-In8/3/20078/3/20078/3/2007 7:47:43 AMAPASS
ok to cover ceiling only
ELE07-02286 Electrical Rough-In8/2/20078/3/20078/3/2007 7:46:24 AMACANC
Phone #: ###-#### Internet Inspection Request from: Steve Craig wrong permit number, called contr, he couldn't get changed in time, added inspection for space 160