FIR06-00959
| INSP-Final Inspection | 8/3/2007 | 8/3/2007 | 8/3/2007 4:30:13 PM | P | DEFR |
|
|
Rescheduled per conversation with contractor.
|
FIR06-00934
| INSP-Final Inspection | 8/3/2007 | 8/3/2007 | 8/3/2007 4:29:25 PM | P | DEFR |
|
|
Inspection rescheduled per conversation with contractor.
|
FIR07-00526
| INSP-Final Inspection | 8/2/2007 | 8/3/2007 | 8/3/2007 4:25:24 PM | P | NR |
|
|
Need to complete c/n and hydrostatic testing prior to final approval.
|
FIR07-00572
| INSP-Sprinkler Rough-in | 8/1/2007 | 8/3/2007 | 8/3/2007 4:24:02 PM | A | PART |
|
|
Third floor classrooms as noted on approved plans are okay for cover, noted one leaking swing joint to be repaired-see plans for location.
|
FIR07-00526
| INSP-Sprinkler Rough-in/Hydro | 8/2/2007 | 8/3/2007 | 8/3/2007 3:12:17 PM | P | FAIL |
|
|
Need one additional EC sw as noted, upright heads at some locations in the studio exceed obstruction tables, need data submittals on vertical sw heads.
|
FIR07-00221
| INSP-Final Inspection | 8/2/2007 | 8/3/2007 | 8/3/2007 3:04:52 PM | A | PASS |
|
|
Fire sprinkler permit final inspection passed.
|
BLD06-01483
| FIRE-Final Inspection | 8/2/2007 | 8/3/2007 | 8/3/2007 12:10:41 PM | A | FAIL |
|
|
Provide approved hardware at the two exit doors-see fire code review notes for requirements, mount the PFE on the wall as discussed.
|
FIR07-00357
| INSP-Final Inspection | 8/2/2007 | 8/3/2007 | 8/3/2007 11:27:49 AM | A | PASS |
|
|
Fire sprinkler permit finaled, noted one missing escutcheon at an office to be installed today per contractor.
|
BLD07-00357
| FIRE-Final Inspection | 8/3/2007 | 8/3/2007 | 8/3/2007 11:26:26 AM | A | FAIL |
|
|
Need project related fire alarm permit final, also missing emergency egress lighting, see fire code review notes for requirements.
|
FIR07-00436
| INSP-Final Inspection | 8/2/2007 | 8/3/2007 | 8/3/2007 11:24:40 AM | A | FAIL |
|
|
Installation matches plan and floor layout, however the conference room has been relocated to an area without av notification. Provide new horn/strobe at this location or move the conference room to its original area.
|
FIR07-00270
| INSP-Final Inspection | 8/3/2007 | 8/3/2007 | 8/3/2007 11:18:58 AM | A | PASS |
|
|
Fire sprinkler permit finaled, one missing escutcheon installed while on site.
|
BLD06-00688
| FIRE-Final Inspection | 8/2/2007 | 8/3/2007 | 8/3/2007 11:17:32 AM | A | PASS |
|
|
Shell and core fire life safety final inspection passed.
|
FIR07-00435
| INSP-Final Inspection | 8/2/2007 | 8/3/2007 | 8/3/2007 11:15:47 AM | A | PASS |
|
|
Fire alarm work completed satisfactory, permit finaled.
|
FIR06-00934
| INSP-Final Inspection | 7/31/2007 | 8/3/2007 | 8/3/2007 10:12:04 AM | A | CANC |
|
|
Final bay 10 Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes
|
FIR06-00959
| INSP-Final Inspection | 7/31/2007 | 8/3/2007 | 8/3/2007 10:11:39 AM | A | CANC |
|
|
Final bay 10 Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes
|