Inspections for the day of: Friday, August 3, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00959 INSP-Final Inspection8/3/20078/3/20078/3/2007 4:30:13 PMPDEFR
Rescheduled per conversation with contractor.
FIR06-00934 INSP-Final Inspection8/3/20078/3/20078/3/2007 4:29:25 PMPDEFR
Inspection rescheduled per conversation with contractor.
FIR07-00526 INSP-Final Inspection8/2/20078/3/20078/3/2007 4:25:24 PMPNR
Need to complete c/n and hydrostatic testing prior to final approval.
FIR07-00572 INSP-Sprinkler Rough-in8/1/20078/3/20078/3/2007 4:24:02 PMAPART
Third floor classrooms as noted on approved plans are okay for cover, noted one leaking swing joint to be repaired-see plans for location.
FIR07-00526 INSP-Sprinkler Rough-in/Hydro8/2/20078/3/20078/3/2007 3:12:17 PMPFAIL
Need one additional EC sw as noted, upright heads at some locations in the studio exceed obstruction tables, need data submittals on vertical sw heads.
FIR07-00221 INSP-Final Inspection8/2/20078/3/20078/3/2007 3:04:52 PMAPASS
Fire sprinkler permit final inspection passed.
BLD06-01483 FIRE-Final Inspection8/2/20078/3/20078/3/2007 12:10:41 PMAFAIL
Provide approved hardware at the two exit doors-see fire code review notes for requirements, mount the PFE on the wall as discussed.
FIR07-00357 INSP-Final Inspection8/2/20078/3/20078/3/2007 11:27:49 AMAPASS
Fire sprinkler permit finaled, noted one missing escutcheon at an office to be installed today per contractor.
BLD07-00357 FIRE-Final Inspection8/3/20078/3/20078/3/2007 11:26:26 AMAFAIL
Need project related fire alarm permit final, also missing emergency egress lighting, see fire code review notes for requirements.
FIR07-00436 INSP-Final Inspection8/2/20078/3/20078/3/2007 11:24:40 AMAFAIL
Installation matches plan and floor layout, however the conference room has been relocated to an area without av notification. Provide new horn/strobe at this location or move the conference room to its original area.
FIR07-00270 INSP-Final Inspection8/3/20078/3/20078/3/2007 11:18:58 AMAPASS
Fire sprinkler permit finaled, one missing escutcheon installed while on site.
BLD06-00688 FIRE-Final Inspection8/2/20078/3/20078/3/2007 11:17:32 AMAPASS
Shell and core fire life safety final inspection passed.
FIR07-00435 INSP-Final Inspection8/2/20078/3/20078/3/2007 11:15:47 AMAPASS
Fire alarm work completed satisfactory, permit finaled.
FIR06-00934 INSP-Final Inspection7/31/20078/3/20078/3/2007 10:12:04 AMACANC
Final bay 10 Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes
FIR06-00959 INSP-Final Inspection7/31/20078/3/20078/3/2007 10:11:39 AMACANC
Final bay 10 Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes