Inspections for the day of: Tuesday, August 3, 2010.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00294 INSP-Final Inspection7/29/20108/3/20108/3/2010 4:19:05 PMANR
FIR10-00293 INSP-Final Inspection7/29/20108/3/20108/3/2010 4:18:41 PMANR
FIR10-00290 INSP-Final Inspection7/29/20108/3/20108/3/2010 4:18:19 PMAFAIL
See plan set for annotations regarding locations of correction items including cd ratings at several areas, SD placement, MP height, duct detector housings at exterior locations, trouble on the panel, item 6 on plan review comments, etc.
FIR10-00254 INSP-Sprinkler Rough-in8/3/20108/3/20108/3/2010 4:13:22 PMPPART
Rough-in at the mezzanines passed inspection. Main tie-in not yet complete due to hydrostatic testing.
FIR10-00349 INSP-Final Inspection8/2/20108/3/20108/3/2010 4:11:41 PMPPART
Overhead system modifications at the tenant remodel are good for cover. Noted one leak at the new mechanical tee in the corridor to be repaired.
FIR10-00340 INSP-Final Inspection8/2/20108/3/20108/3/2010 4:09:10 PMPPART
Pendent head at one room NE corner is below max. allowable distance from the ceiling. Remainder of the scope of work okayed.
BLD10-00294 FIRE-Final Inspection8/2/20108/3/20108/3/2010 4:06:48 PMAFAIL
Door hardware at two locations is not compliant, need to post one PFE at each floor level as discussed.
FIR10-00254 INSP-Sprinkler Rough-in/Hydro8/2/20108/3/20108/3/2010 4:04:53 PMAPART
Overhead hydrostatic test of the new system piping completed satisfactory.
FIR10-00358 INSP-Sprinkler Rough-in8/2/20108/3/20108/3/2010 4:03:29 PMAPART
Correction items verified for completion, overhead fire sprinkler system modifications are good for cover at the drop ceiling.