Inspections for the day of: Wednesday, August 3, 2011.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE11-01752 Electrical Rough-In8/2/20118/3/20118/3/2011 3:20:01 PMPPASS
robert Phone #: ###-#### called electrician to change permit to be in electrical contractor name, not general, ri ok
ELE11-01745 Rough-In Permanent Service8/3/20118/3/20118/3/2011 2:46:09 PMPPASS
Call Dene with any questions
Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser ri ok, p/s u/g n ok
ELE11-01766 Rough-In Permanent Service8/3/20118/3/20118/3/2011 1:57:49 PMPPASS
Please call on when you get there. Thanks Phone #: ###-#### >> Inspection requested via web by TOM BICANDI ri ok, p/s u/g n ok
ELE11-01031 Final8/3/20118/3/20118/3/2011 1:14:43 PMPPASS
this floor is ready for a final. We are on site today working on the 3rd floor. call steve at ###-#### and he will walk you thru the 4th floor work for a final Phone #: ###-#### >> Inspection requested via web by Don Lustig ok final, signed card
ELE11-01746 Permanent Service8/2/20118/3/20118/3/2011 12:37:33 PMPPASS
Service inspection for occupied home. Thank you! Phone #: ###-#### >> Inspection requested via web by Adam Staigle p/s o/h rec ok, at final check ground rods, panel schedule
ELE11-01533 Final7/28/20118/3/20118/3/2011 11:53:59 AMAPASS
dan - please call 1/2 hr prior Phone #: ###-#### ok to final
ELE11-01250 Final8/2/20118/3/20118/3/2011 11:45:28 AMAPASS
dan- ###-#### >> Inspection requested via web by Dan Hobdey corrections made, ok final
ELE11-00572 Permanent Service8/2/20118/3/20118/3/2011 11:18:40 AMAPASS
Dan, ###-####, this was supposed to be finaled months ago- aging permit >> Inspection requested via web by Dan Hobdey ok final
ELE11-01749 Rough-In Permanent Service8/2/20118/3/20118/3/2011 9:23:09 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by daniel bibikov called, left correction notice, NEC 300.4(A)(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 334.23 shall protect wiring within 6' of attic access, 210.52(E) shall provide outlet at front of dwelling, 314.20 boxes in walls of combustible material sjhall be flush with finished surface, QUESTION, any garage door lights,rest ok
ELE11-01753 Rough-In Permanent Service8/2/20118/3/20118/3/2011 8:42:48 AMANH
Phone #: ###-#### >> Inspection requested via web by Dan Rohl called, nobody home, will re-schedule, occupied house
ELE11-01747 Permanent Service8/2/20118/3/20118/3/2011 8:26:44 AMAPASS
If you have any questions, please call Clay. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan p/s o/h n ok
ELE11-01739 Permanent Service8/2/20118/3/20118/3/2011 7:39:14 AMAPASS
Ayn Phone #: ###-#### p/s, exst meter pak, rec, ok
ELE11-00144 ELE-Aging Inspection8/3/20118/3/20118/3/2011 6:33:37 AM DONE
still under construction