Inspections for the day of: Wednesday, August 3, 2011.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD11-01243 FIRE-Final Inspection8/2/20118/3/20118/4/2011 6:22:54 AMACANC
duplicate inspection
BLD11-01243 FIRE-Final Inspection8/2/20118/3/20118/3/2011 3:04:36 PMAPART
IA temporary occupancy was given with steve kieters permission. The items needing addressed are removing the wood bar across the northwest exit door, provide single action hardware for both the active and inactive leaves of the secondary front exit doors and removing the thumbturn and the manual flush bolts from the east exit door. I went over possible options with the owner Zach. One of which was providing keyed hardware on the east non required exit and placing a display in front of the door.
BLD11-01702 FIRE-Final Inspection8/2/20118/3/20118/3/2011 2:02:15 PMAPASS
life safety passed
FIR11-00339 INSP-Sprinkler Rough-in8/2/20118/3/20118/3/2011 10:50:27 AMAPASS
Piping is ok to cover.
BLD11-01702 FIRE-Conference8/3/20118/3/20118/3/2011 9:21:06 AMADONE
I went over life safety requirements with the general contractor. Duct smoke detectors have been mounted to the two return ducts but never wired up. Per the original HVAC contractor the hvac units are only 3 1/2 ton and do not require the detectors. The contractor and I agreed to just remove them. Also need fire extinguishers and the remaining round door knob in the basement changed to lever type.
FIR11-00159 INSP-Sprinkler Rough-in/Hydro8/2/20118/3/20118/2/2011 12:00:00 AMACANC
Hydo//Joe ###-#### -- cancelled per Troy Cobbley 8/2/11 leg