Inspections for the day of: Monday, August 3, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02472 ELE-Aging Inspection8/3/20158/3/20158/4/2015 3:40:33 PM DONE
Still under construction
ELE15-02386 Conference8/3/20158/3/20158/3/2015 4:04:50 PMPDONE
conference to discuss location of new meter pack, please call ahead so we can meet there Phone #: ###-#### Inspection requested via web by Lee VanSchoiack Discussed a location of additional meters to be added to building about 20' to the east of original location. Checked with Daryl Degrange and as long as number of disconnecting means does not exceed 6 location would be acceptable.
ELE15-02392 Final8/3/20158/3/20158/3/2015 1:52:41 PMPNH
Call Meko Myers for access ###-#### Phone #: ###-#### Inspection requested via web by jamie berg Left message will reschedule
ELE15-02270 Final8/3/20158/3/20158/3/2015 1:26:54 PMPPASS
JR Phone #: ###-#### Final ok
ELE15-01292 Conference7/31/20158/3/20158/3/2015 12:53:08 PMADONE
Call two hours before // Jason Phone #: ###-#### Discussed correction from previous inspection.
ELE15-01292 Electrical Rough-In8/3/20158/3/20158/3/2015 12:39:52 PMPPASS
Call two hours before // Jason Phone #: ###-#### Rough in ok cover
ELE15-01586 Final7/31/20158/3/20158/3/2015 10:22:03 AMPPASS
Install wall sign reading Allied Envelope. All primary power by others Phone #: ###-#### Inspection requested via web by Ken Olsen UL listing and disconnecting means confirmed. Final ok
ELE15-02270 Final7/31/20158/3/20158/3/2015 9:54:59 AMAFAIL
JR Phone #: ###-#### 210.8- All 120 volt 15 and 20 amp receptacle outlets shall have GFCI protection
ELE15-02204 Rough-In Permanent Service7/31/20158/3/20158/3/2015 9:21:05 AMAPASS
Gary is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
ELE15-02349 Permanent Service7/31/20158/3/20158/3/2015 8:32:59 AMAFAIL
Chris Phone #: ###-#### 250.53- Grounding electrode conductor not connected to 1st ground rod. 250.122- All strands of equipment grounding conductor shall terminate in lug. Unable to leave message due to full mailbox at contact number