Inspections for the day of: Monday, August 3, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorThomas Walsh
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00603 INSP-Sprinkler Rough-in8/3/20158/3/20158/4/2015 12:42:25 PMPCANC
Due to time constraints, this inspection could ntot be completed. Will reschedule for 8/4.
FIR14-00815 INSP-Sprinkler Rough-in8/3/20158/3/20158/4/2015 12:34:04 PMPPASS
This is a trip test dry system trip for 4/1 north.
FIR14-00898 INSP-Final Inspection8/3/20158/3/20158/4/2015 12:28:26 PMPCANC
Canceled fire alarm testing for today - rescheduled for tomorrow (8/4).
BLD13-02424 FIRE-Conference8/3/20158/3/20158/4/2015 12:26:11 PMPDONE
\Meeting with GC and Elect. contractor to review exit signs for clubhouse, corridors, and parking garage. See plans for areas where additional signs are required, and where exit signs need to be relocated.
FIR14-00815 INSP-Final Inspection8/3/20158/3/20158/3/2015 2:15:49 PMPCANC
Final inspection pending completion and passing of all dry pipe systems.
FIR13-00724 INSP-Alarm Testing7/30/20158/3/20158/3/2015 2:14:26 PMPCANC
No inspections called in for this permit.
FIR14-00365 INSP-Sprinkler Rough-in/Hydro7/31/20158/3/20158/3/2015 2:13:01 PMPPASS
Fire pump commissioning test with MFG's rep. Tested 0 flow. 100% and 150% with generator and both supplies open. All tested OK. Pump test report to e emailed to Tim Frost.
FIR14-00813 INSP-Final Inspection7/31/20158/3/20158/3/2015 2:10:55 PMPCANC
6th floor H&D system not ready for test yet. Exhaust system not completed.
FIR14-00328 INSP-Final Inspection7/31/20158/3/20158/3/2015 2:10:00 PMPPART
First floor kitchen hood and duct system test, including balloon test, MP, detection gas/electric shutoffs, nozzles types, etc.
Alltested OK
NOTE: Nozzle placement may have to be modified to point in the locations per the manual (center of appliance). Also, may need to have a barier between the DF fryer and the gas range - currently 6" with no barrier.
FIR13-00724 INSP-Alarm Testing7/30/20158/3/20158/3/2015 2:07:06 PMAPART
Initial fire alarm system testing, including test of notification (speaker/strobes) throuout the JUMP bldg. including the U/G parking garage the above ground parking garage, the helix and all rooms above grade. A few devices were not very load, and the contractor agreed to modify the devices in these areas to improve audibility.
Also tested fire pump functions to coincide with the fire pump commissioning test. Also tested one (1) H&D system test for the 1st floor kitchen.
NOTE: Elevators, HVAC, and FSDs not ready for test yet.