ELE12-00179
| ELE-Aging Inspection | 8/3/2016 | 8/3/2016 | 8/5/2016 6:46:01 AM | | CANC |
|
|
|
ELE16-02303
| Final | 8/3/2016 | 8/3/2016 | 8/3/2016 3:04:40 PM | P | PASS |
|
|
Kyle Phone #: ###-#### Final ok
|
ELE15-03901
| Electrical Rough-In | 8/3/2016 | 8/3/2016 | 8/3/2016 2:33:25 PM | P | PART |
|
|
Call Pierce for pre-walk final of 8th floor. Phone #: ###-#### Inspection requested via web by Rafael Castillo TCO of 8th floor 300.15 all boxes shall have covers. LV data, and card readers. 300.21- All electrical penetrations in firewalls shall be sealed with fire resistant materials. check all north side offices noticed. Cover boxes in firewall near N. stair. 110.3- Open neutral LR8D-32 center outlet in eating area off break room. Stair lighting on stair from 8 to 9 not complete. OK to install furniture
|
ELE15-01348
| Electrical Rough-In | 8/2/2016 | 8/3/2016 | 8/3/2016 12:05:44 PM | P | PASS |
|
|
Emergency Generator EG-C 1600A, EMSBB GEN. DIST.,T-EQGEN1,EQ-GEN 1 Branch circuit panel, Branch circuits fed from EQGEN 1 ROOM # OBG111 Phone #: ###-#### Inspection requested via web by Tom Betty Gen set main bonding jumper installed at factory, Tom to remove main bonding jumper at ATS LS and ATS EQ. Gen set and associated gear noted rough in ok cover
|
ELE16-01838
| Electrical Rough-In | 8/2/2016 | 8/3/2016 | 8/3/2016 12:03:20 PM | A | PASS |
|
|
SWHQ Level 2 Stack 1 RM # 216, 221,222,218,223 Wall R-I Phone #: ###-#### Inspection requested via web by Tom Betty Walls as noted rough in ok cover
|
ELE15-01348
| Electrical Rough-In | 8/2/2016 | 8/3/2016 | 8/3/2016 12:02:42 PM | A | PASS |
|
|
level 3 core ceiling, women''s bathroom ( where 3 can lights were missing ), possibly level 4 core ceiling. Phone #: ###-#### Inspection requested via web by Brandon Robinson Level 3 womens bath lid complete rough in ok cover, elevator lobby on 1, and 3 wall and ceiling rough in ok cover.
|
ELE15-02740
| Electrical Rough-In | 8/2/2016 | 8/3/2016 | 8/3/2016 10:52:24 AM | A | PASS |
|
|
Seth Phone #: ###-#### Level 1 Front office covered prior to inspection. Outdoor covered entrance to shange UF to MC where attached to building surface as per 334.12, Back corridor grid rough in ok cover
|
ELE15-03478
| Final | 8/2/2016 | 8/3/2016 | 8/3/2016 10:28:54 AM | A | FAIL |
|
|
garage code is 1234 please call if you have any questions. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman 110.22- Furnace disconnecting means shall be identified as to its purpose. 210.8- All 15 and 20 amp receptacle outlets shall have GFCI protection. 300.21- Openings around electrical penetrations shall be sealed with fire resistant materials. Garage warm wall. 440.22- AC max overcurrent 25 amp, 30 amp installed.
|
ELE16-01477
| Electrical Rough-In | 8/2/2016 | 8/3/2016 | 8/3/2016 9:47:12 AM | A | PASS |
|
|
Ceiling inspection in the pharmacy in the AM if possible call cody for questions ###-#### thanks Phone #: ###-#### Inspection requested via web by Shane Lott Grid area noted rough in ok cover
|
ELE16-02517
| Rough-In Permanent Service | 8/3/2016 | 8/3/2016 | 8/3/2016 9:17:12 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Rough in ok cover p/s o/h n ok
|
ELE16-02494
| Temporary Service | 8/2/2016 | 8/3/2016 | 8/3/2016 8:51:03 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mike Cole t/s u/g n ok
|
ELE16-01276
| Electrical Rough-In | 8/2/2016 | 8/3/2016 | 8/3/2016 7:39:47 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Mark M Inspection cancelled from web by: Mark M
|