Inspections for the day of: Wednesday, August 3, 2016.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00179 ELE-Aging Inspection8/3/20168/3/20168/5/2016 6:46:01 AM CANC
ELE16-02303 Final8/3/20168/3/20168/3/2016 3:04:40 PMPPASS
Kyle Phone #: ###-#### Final ok
ELE15-03901 Electrical Rough-In8/3/20168/3/20168/3/2016 2:33:25 PMPPART
Call Pierce for pre-walk final of 8th floor. Phone #: ###-#### Inspection requested via web by Rafael Castillo
TCO of 8th floor
300.15 all boxes shall have covers. LV data, and card readers.
300.21- All electrical penetrations in firewalls shall be sealed with fire resistant materials. check all north side offices noticed. Cover boxes in firewall near N. stair.
110.3- Open neutral LR8D-32 center outlet in eating area off break room.
Stair lighting on stair from 8 to 9 not complete.
OK to install furniture
ELE15-01348 Electrical Rough-In8/2/20168/3/20168/3/2016 12:05:44 PMPPASS
Emergency Generator EG-C 1600A, EMSBB GEN. DIST.,T-EQGEN1,EQ-GEN 1 Branch circuit panel, Branch circuits fed from EQGEN 1 ROOM # OBG111 Phone #: ###-#### Inspection requested via web by Tom Betty
Gen set main bonding jumper installed at factory, Tom to remove main bonding jumper at ATS LS and ATS EQ. Gen set and associated gear noted rough in ok cover
ELE16-01838 Electrical Rough-In8/2/20168/3/20168/3/2016 12:03:20 PMAPASS
SWHQ Level 2 Stack 1 RM # 216, 221,222,218,223 Wall R-I Phone #: ###-#### Inspection requested via web by Tom Betty Walls as noted rough in ok cover
ELE15-01348 Electrical Rough-In8/2/20168/3/20168/3/2016 12:02:42 PMAPASS
level 3 core ceiling, women''s bathroom ( where 3 can lights were missing ),
possibly level 4 core ceiling. Phone #: ###-#### Inspection requested via web by Brandon Robinson
Level 3 womens bath lid complete rough in ok cover, elevator lobby on 1, and 3 wall and ceiling rough in ok cover.
ELE15-02740 Electrical Rough-In8/2/20168/3/20168/3/2016 10:52:24 AMAPASS
Seth Phone #: ###-####
Level 1 Front office covered prior to inspection. Outdoor covered entrance to shange UF to MC where attached to building surface as per 334.12, Back corridor grid rough in ok cover
ELE15-03478 Final8/2/20168/3/20168/3/2016 10:28:54 AMAFAIL
garage code is 1234 please call if you have any questions. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman
110.22- Furnace disconnecting means shall be identified as to its purpose.
210.8- All 15 and 20 amp receptacle outlets shall have GFCI protection.
300.21- Openings around electrical penetrations shall be sealed with fire resistant materials. Garage warm wall.
440.22- AC max overcurrent 25 amp, 30 amp installed.
ELE16-01477 Electrical Rough-In8/2/20168/3/20168/3/2016 9:47:12 AMAPASS
Ceiling inspection in the pharmacy in the AM if possible call cody for questions ###-#### thanks Phone #: ###-#### Inspection requested via web by Shane Lott Grid area noted rough in ok cover
ELE16-02517 Rough-In Permanent Service8/3/20168/3/20168/3/2016 9:17:12 AMAPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI
Rough in ok cover p/s o/h n ok
ELE16-02494 Temporary Service8/2/20168/3/20168/3/2016 8:51:03 AMAPASS
Phone #: ###-#### Inspection requested via web by Mike Cole
t/s u/g n ok
ELE16-01276 Electrical Rough-In8/2/20168/3/20168/3/2016 7:39:47 AMACANC
Phone #: ###-#### >> Inspection requested via web by Mark M Inspection cancelled from web by: Mark M