BLD18-01159
| FIRE-Final Inspection | 8/2/2018 | 8/3/2018 | 8/3/2018 2:37:23 PM | A | FAIL |
|
|
All fire alarms have to be active in area of work. A FIR permit is required for work that has been completed in area of work. Life fire safety inspection will can not be completed until fire alarm permit issue is resolved. No occupancy is allowed until fire life safety is completed and passed.
Tim Phone #: ###-####
|
FIR18-00518
| INSP-Conference | 8/2/2018 | 8/3/2018 | 8/3/2018 1:21:05 PM | P | CANC |
|
|
Conference canceeld per conversatin with point of contact, conference will be scheduled for a later date.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
FIR18-00507
| INSP-Final Inspection | 8/1/2018 | 8/3/2018 | 8/3/2018 11:54:18 AM | P | PASS |
|
|
Final fire alarm inspection for area of work complete.
Jason Phone #: ###-####
|
FIR18-00373
| INSP-Sprinkler Rough-in/Hydro | 8/2/2018 | 8/3/2018 | 8/3/2018 10:22:46 AM | A | DONE |
|
|
Hydrostatic test for undergorund supply witnessed, no pressure loss observed at riser provided gauge.
UG hydro // Gabe Phone #: ###-####
|
FIR18-00445
| INSP-Final Inspection | 8/2/2018 | 8/3/2018 | 8/2/2018 3:39:49 PM | A | CANC |
|
|
This final inspection will be just for the basement kitchen hood, not the upstairs portion. Peter Naumov ###-####. Please call when the inspector is headed over to the location. Phone #: ###-#### >> Inspection requested via web by Laura Tyson Inspection cancelled from web by: Laura Tyson
|