FIR02-00249
| INSP-Final Inspection | 8/26/2002 | 8/30/2002 | 8/30/2002 12:00:00 AM | A | CANC |
|
|
cancelled by contractor 8/30/2002 8:04:12 AM
|
FIR02-00178
| INSP-Supply line flush | 8/29/2002 | 8/30/2002 | 8/30/2002 12:00:00 AM | A | PASS |
|
|
underground supply line flush and hydro test OK 8/30/2002 10:40:36 AM
|
BLD02-00311
| FIRE-Conference | 8/29/2002 | 8/30/2002 | 8/30/2002 12:00:00 AM | A | NR |
|
|
No approved plans on site and it doesn't appear the plans have even been submitted 8/30/2002 12:30:42 PM
|
BLD02-01648
| FIRE-Final Inspection | 8/29/2002 | 8/30/2002 | 8/30/2002 12:00:00 AM | A | PASS |
|
|
fire life/safety finaled 8/30/2002 9:57:40 AM
|
FIR02-00244
| INSP-Final Inspection | 8/29/2002 | 8/30/2002 | 8/30/2002 12:00:00 AM | A | FAIL |
|
|
"work room" will be used as storage and therefore will be considered ordinary hazard occupancy which means the sprinkler pendants are overspaced. 130sq ft max. Also the shelves only allow 16" of clearance instead of the 18" required. The sprinklers will need to be space to the shelves 8/30/2002 2:34:31 PM
|