Inspections for the day of: Monday, August 30, 2004.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS04-00080 FIR-Final8/27/20048/30/20048/30/2004 12:00:00 AMAFAIL
joe; Phone #: ###-#### Internet Inspection Request from: Annette Moore Pending structural approval 8/30/2004 9:57:22 AM
MIS04-00079 FIR-Final8/27/20048/30/20048/30/2004 12:00:00 AMAFAIL
joe; Phone #: ###-#### Internet Inspection Request from: Annette Moore Pending structural final 8/30/2004 9:57:01 AM
MIS04-00078 FIR-Final8/27/20048/30/20048/30/2004 12:00:00 AMAFAIL
joe; Phone #: ###-#### Internet Inspection Request from: Annette Moore Sprinklers overspaced (over 9 ft) from end of hallway 8/30/2004 9:56:46 AM
MIS04-00081 FIR-Final8/27/20048/30/20048/30/2004 12:00:00 AMAFAIL
joe; Phone #: ###-#### Internet Inspection Request from: Annette Moore Storage too high in storage room - must be 18 inches below sprinklers 8/30/2004 9:56:09 AM
BLD03-02057 FIRE-Final Inspection8/30/20048/30/20048/30/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 8/30/2004 at 10:07:48 AM. Contact: ###-####.
BLD03-02058 FIRE-Final Inspection8/30/20048/30/20048/30/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 8/30/2004 at 10:09:28 AM. Contact: ###-####.
BLD04-00940 FIRE-Final Inspection8/30/20048/30/20048/30/2004 12:00:00 AMPPART
Temp approved per Dave Miller pending fire alarm permits issued and testing 8/30/2004 1:52:30 PM
FIR04-00507 INSP-Final Inspection8/25/20048/30/20048/30/2004 12:00:00 AMPPASS
Please call Scott Carter at least one hour in advance to set up an accurate time to meet. Thanks; Phone #: ###-#### Internet Inspection Request from: Scott Carter II