Inspections for the day of: Tuesday, August 30, 2005.
Number of inspections: 24
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00124 INSP-Final Inspection8/29/20058/30/20059/2/2005 4:07:38 PMAPASS
Attic spacing issues have been corrected and inspected, permit finaled.
FIR05-00424 INSP-Supply line flush8/30/20058/30/20058/31/2005 4:38:57 PMPPART
This inspection was for an underground hydro test which passed.
BLD05-00439 FIRE-Conference8/29/20058/30/20058/31/2005 1:59:53 PMPDONE
On site discussion with Tom from CM company regarding fire lane curb painting.
FIR05-00355 INSP-Supply line flush8/30/20058/30/20058/31/2005 1:38:55 PMPPART
This inspection was for an underground hydrostatic test which passed.
BLD05-02038 FIRE-Final Inspection8/30/20058/30/20058/31/2005 10:32:40 AMPCANC
Inspection to be performed on 8/31.
FIR05-00513 INSP-Sprinkler Rough-in/Hydro8/30/20058/30/20058/31/2005 12:00:00 AMPPART
Hard lid restroom (1 head) cover only.

Scheduled by a contractor via Hello! on 8/30/2005 at 10:29:00 AM. Contact: ###-####.
BLD05-01317 FIRE-Final Inspection8/30/20058/30/20058/30/2005 5:08:28 PMPFAIL
Need to final fire sprinkler permit prior to life safety sign off.
BLD05-01314 FIRE-Conference8/30/20058/30/20058/30/2005 5:04:12 PMPCANC
No time for this confrence today, spoke with the contractor to reschedule for a later date.
BLD05-01200 FIRE-Final Inspection8/30/20058/30/20058/30/2005 5:02:31 PMPFAIL
Provide approved hardware at SE exit door per fire code review note #7 as discussed.
FIR05-00452 INSP-Final Inspection8/29/20058/30/20058/30/2005 5:00:47 PMPPASS
Fire alarm passed field inspection.
FIR05-00394 INSP-Final Inspection8/30/20058/30/20058/30/2005 3:17:56 PMPCANC
No time for inspection, Grant will reschedule for tomorrow per our conversation.
FIR05-00390 INSP-Final Inspection8/30/20058/30/20058/30/2005 3:15:57 PMPCANC
No time to perform this inspection today. Orlen to reschedule for this friday per our agreement.
FIR05-00343 INSP-Final Inspection8/29/20058/30/20058/30/2005 3:13:17 PMPPASS
Elevator #7 upgrade passed inspection, fire alarm finaled.
FIR05-00044 INSP-Alarm Testing8/29/20058/30/20058/30/2005 1:24:52 PMAPART
Partial inspection performed on area B, tested smoke and heat detectors, manual pull stations, and horn strobes, still need to test duct smoke detectors, battery, phone lines.
BLD05-00874 FIRE-Final Inspection8/29/20058/30/20058/30/2005 11:47:34 AMAPASS
Exit sign and emergency lights are operable, life safety finaled.
FIR05-00443 INSP-Sprinkler Rough-in8/29/20058/30/20058/30/2005 11:24:12 AMAPART
Overhead rough-in is good for cover, can final permit when ceiling tile with escutcheons are installed.
FIR05-00186 INSP-Final Inspection8/29/20058/30/20058/30/2005 10:36:32 AMACANC
No time available for this inspection today, ray to schedule for tomorrow at 9:00am per our agreement.
BLD05-01440 FIRE-Final Inspection8/29/20058/30/20058/30/2005 10:34:06 AMAPASS
Fire life safety is satisfactory.
FIR05-00198 INSP-Final Inspection8/29/20058/30/20058/30/2005 10:16:57 AMACANC
No time available today for this inspection, spoke with linda from mountain alarm at ###-####, she will reschedule inspection for next week.
FIR05-00469 INSP-Sprinkler Rough-in8/26/20058/30/20058/30/2005 10:06:41 AMAFAIL
The installed SW heads are quick response and do not match the standard response SW heads as submitted on the city approved documents for this project.
FIR05-00439 INSP-Sprinkler Rough-in8/26/20058/30/20058/30/2005 10:01:29 AMAFAIL
Spacing is incorrect for the added heads, installation does not match approved plans, existing SW heads will cold solder the added pendants at duct work.
BLD05-00232 FIRE-Final Inspection8/29/20058/30/20058/30/2005 9:57:45 AMAPASS
Life safety passed inspection.
FIR05-00436 INSP-Final Inspection8/29/20058/30/20058/30/2005 8:54:31 AMAPASS
New dry pipe valve operated correctly, permit finaled.
FIR05-00419 INSP-Final Inspection8/30/20058/30/20058/30/2005 12:00:00 AMAPASS
Fire sprinkler permit finaled.