Inspections for the day of: Thursday, August 30, 2007.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02501 Final8/30/20078/30/20078/30/2007 3:36:36 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Dan Surerus wiring for switches and wall fixtures in patient rms shall meet 517.13(A&B) see added r/i
ELE07-02501 Electrical Rough-In8/30/20078/30/20078/30/2007 3:35:06 PMPPART
Phone #: ###-#### Internet Inspection Request from: Dan Surerus ceiling ok for tiles
ELE07-03035 Rough-In Permanent Service8/30/20078/30/20078/30/2007 3:00:45 PMPFAIL
Please call at least 20 mins prior to inspection--darrell ###-#### called corr no screws allowed in plastic boxes, needs outlet for wall space kit wall entry by refer
ELE07-02299 Final8/30/20078/30/20078/30/2007 2:22:32 PMPFAIL
terry; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt
314,23 all boxes shall be supported 362.30&330.30 all ent and mc shall secured at boxes and supported , remove ceiling tiles, install show windoe outlets, support all fixtures with wires called left message
ELE07-03021 Electrical Rough-In8/30/20078/30/20078/30/2007 1:37:33 PMPPART
Trent; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
walls ok
ELE07-03045 Electrical Rough-In8/30/20078/30/20078/30/2007 12:59:33 PMPFAIL
PLease call at least 30 mins prior to inspection so he can meet ya there--Don ###-#### shall not use romex for commercial work
ELE07-03008 Temporary Service8/30/20078/30/20078/30/2007 12:58:51 PMAPASS
Thank jack - Jerry will have done by 8:30. Phone #: ###-#### Internet Inspection Request from: Tracy Robertson t/s u/g new ok
ELE07-03010 Temporary Service8/30/20078/30/20078/30/2007 12:58:28 PMAPASS
Thanks Jack - Jerry to have completed by 8:30. Phone #: ###-#### Internet Inspection Request from: Tracy Robertson t/s u/g new ok
ELE07-01438 Final8/29/20078/30/20078/30/2007 11:38:11 AMAPASS
PLEASE CLOSE THIS OUT; ANOTHER CONTRACTOR WIRED THE POOL EQUIPMENT Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack
ELE07-00573 Electrical Rough-In8/30/20078/30/20078/30/2007 11:30:11 AMAPASS
Scheduled by a contractor via Hello! on 8/30/2007 at 7:12:22 AM. Contact: ###-####.
. 1. ri as noted on prints ok. .
ELE07-02929 Temporary Service8/29/20078/30/20078/30/2007 10:59:51 AMAPART
darlene Phone #: ###-#### t/s o/h new ok
ELE07-02645 Final8/29/20078/30/20078/30/2007 10:28:32 AMAPASS
2 circuits to power pole. Please call Town & Country directly for any questions. Thank you. Phone #: ###-#### Internet Inspection Request from: Margaret Roye
ELE07-02864 Electrical Rough-In8/29/20078/30/20078/30/2007 10:03:31 AMAFAIL
Please call prior to arrival. Ins. for Kitchen/nook remodel rough-in Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr fee due called 210.52(C)(1) shall maintain outlet spacingletf of kit sink, 210.52(A) outlet spacing wall din rm 210.52(B)(2) micro wave and under counter light not allowed on SABC250.140,134,138 needs 4 wire insulated neutral to oven, also no buried splices (phone cable)
ELE07-03030 Electrical Rough-In8/30/20078/30/20078/30/2007 9:05:57 AMPCANC
reinspect; Luke; Phone #: ###-#### Internet Inspection Request from: Hattie James called told contr shall not request inspection if job not complete and ready
ELE07-02709 Final8/29/20078/30/20078/30/2007 9:02:59 AMAPASS
ready for final on this project (Plato''s)please call if any questions thank you Phone #: ###-#### Internet Inspection Request from: Brad Baker ok card signed
ELE07-03030 Electrical Rough-In8/29/20078/30/20078/30/2007 8:37:45 AMAFAIL
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James no access called check panel for breaker over 6ft 7" needs recept within 25ft of a/c
ELE07-00620 Final8/29/20078/30/20078/30/2007 8:04:35 AMAPASS
this permit should have been finaled out back in March when the corrections were made and reinspection was called in race way to track portion of lights were installed Phone #: ###-#### Internet Inspection Request from: Brad Baker
ELE06-03281 Final8/29/20078/30/20078/30/2007 7:24:55 AMPCANC
Please inspect for final in A and B wings. Thank you. Phone #: ###-#### Internet Inspection Request from: Jim Friend Inspection cancelled from web by: Jim Friend
ELE06-03280 Final8/29/20078/30/20078/30/2007 7:24:47 AMPCANC
Please inspect for final in D-wing. Thank you. Phone #: ###-#### Internet Inspection Request from: Jim Friend Inspection cancelled from web by: Jim Friend
ELE06-02704 Final8/29/20078/30/20078/30/2007 7:24:36 AMPCANC
Please inspect for C-wing final C of O. Thank you. Phone #: ###-#### Internet Inspection Request from: Jim Friend Inspection cancelled from web by: Jim Friend
ELE07-03018 Final8/29/20078/30/20078/29/2007 2:30:54 PMACANC
Final Inspection Hot Tub Installation Phone #: ###-#### Internet Inspection Request from: Kelly Felin Inspection cancelled from web by: Kelly Felin