ELE07-02501
| Final | 8/30/2007 | 8/30/2007 | 8/30/2007 3:36:36 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Surerus wiring for switches and wall fixtures in patient rms shall meet 517.13(A&B) see added r/i
|
ELE07-02501
| Electrical Rough-In | 8/30/2007 | 8/30/2007 | 8/30/2007 3:35:06 PM | P | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Surerus ceiling ok for tiles
|
ELE07-03035
| Rough-In Permanent Service | 8/30/2007 | 8/30/2007 | 8/30/2007 3:00:45 PM | P | FAIL |
|
|
Please call at least 20 mins prior to inspection--darrell ###-#### called corr no screws allowed in plastic boxes, needs outlet for wall space kit wall entry by refer
|
ELE07-02299
| Final | 8/30/2007 | 8/30/2007 | 8/30/2007 2:22:32 PM | P | FAIL |
|
|
terry; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt 314,23 all boxes shall be supported 362.30&330.30 all ent and mc shall secured at boxes and supported , remove ceiling tiles, install show windoe outlets, support all fixtures with wires called left message
|
ELE07-03021
| Electrical Rough-In | 8/30/2007 | 8/30/2007 | 8/30/2007 1:37:33 PM | P | PART |
|
|
Trent; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt walls ok
|
ELE07-03045
| Electrical Rough-In | 8/30/2007 | 8/30/2007 | 8/30/2007 12:59:33 PM | P | FAIL |
|
|
PLease call at least 30 mins prior to inspection so he can meet ya there--Don ###-#### shall not use romex for commercial work
|
ELE07-03008
| Temporary Service | 8/30/2007 | 8/30/2007 | 8/30/2007 12:58:51 PM | A | PASS |
|
|
Thank jack - Jerry will have done by 8:30. Phone #: ###-#### Internet Inspection Request from: Tracy Robertson t/s u/g new ok
|
ELE07-03010
| Temporary Service | 8/30/2007 | 8/30/2007 | 8/30/2007 12:58:28 PM | A | PASS |
|
|
Thanks Jack - Jerry to have completed by 8:30. Phone #: ###-#### Internet Inspection Request from: Tracy Robertson t/s u/g new ok
|
ELE07-01438
| Final | 8/29/2007 | 8/30/2007 | 8/30/2007 11:38:11 AM | A | PASS |
|
|
PLEASE CLOSE THIS OUT; ANOTHER CONTRACTOR WIRED THE POOL EQUIPMENT Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack
|
ELE07-00573
| Electrical Rough-In | 8/30/2007 | 8/30/2007 | 8/30/2007 11:30:11 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 8/30/2007 at 7:12:22 AM. Contact: ###-####. . 1. ri as noted on prints ok. .
|
ELE07-02929
| Temporary Service | 8/29/2007 | 8/30/2007 | 8/30/2007 10:59:51 AM | A | PART |
|
|
darlene Phone #: ###-#### t/s o/h new ok
|
ELE07-02645
| Final | 8/29/2007 | 8/30/2007 | 8/30/2007 10:28:32 AM | A | PASS |
|
|
2 circuits to power pole. Please call Town & Country directly for any questions. Thank you. Phone #: ###-#### Internet Inspection Request from: Margaret Roye
|
ELE07-02864
| Electrical Rough-In | 8/29/2007 | 8/30/2007 | 8/30/2007 10:03:31 AM | A | FAIL |
|
|
Please call prior to arrival. Ins. for Kitchen/nook remodel rough-in Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr fee due called 210.52(C)(1) shall maintain outlet spacingletf of kit sink, 210.52(A) outlet spacing wall din rm 210.52(B)(2) micro wave and under counter light not allowed on SABC250.140,134,138 needs 4 wire insulated neutral to oven, also no buried splices (phone cable)
|
ELE07-03030
| Electrical Rough-In | 8/30/2007 | 8/30/2007 | 8/30/2007 9:05:57 AM | P | CANC |
|
|
reinspect; Luke; Phone #: ###-#### Internet Inspection Request from: Hattie James called told contr shall not request inspection if job not complete and ready
|
ELE07-02709
| Final | 8/29/2007 | 8/30/2007 | 8/30/2007 9:02:59 AM | A | PASS |
|
|
ready for final on this project (Plato''s)please call if any questions thank you Phone #: ###-#### Internet Inspection Request from: Brad Baker ok card signed
|
ELE07-03030
| Electrical Rough-In | 8/29/2007 | 8/30/2007 | 8/30/2007 8:37:45 AM | A | FAIL |
|
|
Tom; Phone #: ###-#### Internet Inspection Request from: Hattie James no access called check panel for breaker over 6ft 7" needs recept within 25ft of a/c
|
ELE07-00620
| Final | 8/29/2007 | 8/30/2007 | 8/30/2007 8:04:35 AM | A | PASS |
|
|
this permit should have been finaled out back in March when the corrections were made and reinspection was called in race way to track portion of lights were installed Phone #: ###-#### Internet Inspection Request from: Brad Baker
|
ELE06-03281
| Final | 8/29/2007 | 8/30/2007 | 8/30/2007 7:24:55 AM | P | CANC |
|
|
Please inspect for final in A and B wings. Thank you. Phone #: ###-#### Internet Inspection Request from: Jim Friend Inspection cancelled from web by: Jim Friend
|
ELE06-03280
| Final | 8/29/2007 | 8/30/2007 | 8/30/2007 7:24:47 AM | P | CANC |
|
|
Please inspect for final in D-wing. Thank you. Phone #: ###-#### Internet Inspection Request from: Jim Friend Inspection cancelled from web by: Jim Friend
|
ELE06-02704
| Final | 8/29/2007 | 8/30/2007 | 8/30/2007 7:24:36 AM | P | CANC |
|
|
Please inspect for C-wing final C of O. Thank you. Phone #: ###-#### Internet Inspection Request from: Jim Friend Inspection cancelled from web by: Jim Friend
|
ELE07-03018
| Final | 8/29/2007 | 8/30/2007 | 8/29/2007 2:30:54 PM | A | CANC |
|
|
Final Inspection Hot Tub Installation Phone #: ###-#### Internet Inspection Request from: Kelly Felin Inspection cancelled from web by: Kelly Felin
|