Inspections for the day of: Thursday, August 30, 2007.
Number of inspections: 35
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-01014 BLD-Other8/30/20078/30/200712/27/2007 12:00:00 AMADONE
LS
BLD07-00349 FIRE-Conference8/28/20078/30/20079/6/2007 1:13:30 PMADEFR
william Phone #: ###-####
BLD06-02542 FIRE-Final Inspection8/29/20078/30/20078/31/2007 1:11:52 PMAFAIL
No access provided to check defficiency at unit 206.
BLD07-00981 FIRE-Final Inspection8/30/20078/30/20078/30/2007 6:18:53 PMPPASS
Fire life safety final inspection passed.
FIR07-00690 INSP-Final Inspection8/30/20078/30/20078/30/2007 6:17:24 PMPPASS
Fire alarm permit finaled.
FIR07-00690 INSP-Alarm Testing8/29/20078/30/20078/30/2007 6:13:49 PMAPASS
Required corrections verified, fire alarm testing passed.
FIR07-00610 INSP-Final Inspection8/30/20078/30/20078/30/2007 6:04:04 PMPCANC
Overbooked
BLD06-02674 FIRE-Final Inspection8/30/20078/30/20078/30/2007 6:03:32 PMPCANC
Overbooked
FIR06-00011 INSP-Alarm Testing8/30/20078/30/20078/30/2007 6:01:37 PMPCANC
Overbooked
BLD07-01969 FIRE-Final Inspection8/30/20078/30/20078/30/2007 6:01:01 PMPCANC
Overbooked
FIR07-00304 INSP-Sprinkler Rough-in8/29/20078/30/20078/30/2007 6:00:16 PMPCANC
Overbooked
FIR07-00351 INSP-Sprinkler Rough-in/Hydro8/29/20078/30/20078/30/2007 5:59:37 PMACANC
Overbooked
FIR07-00015 INSP-Alarm Testing8/29/20078/30/20078/30/2007 5:58:56 PMACANC
Overbooked
BLD07-02058 FIRE-Conference8/29/20078/30/20078/30/2007 5:57:16 PMACANC
Overbooked
FIR07-00234 INSP-Sprinkler Rough-in8/29/20078/30/20078/30/2007 5:56:28 PMACANC
Overbooked
FIR07-00501 INSP-Sprinkler Rough-in/Hydro8/29/20078/30/20078/30/2007 5:55:27 PMACANC
Overbooked
BLD07-00792 FIRE-Conference8/29/20078/30/20078/30/2007 5:54:52 PMACANC
Overbooked
FIR05-00536 INSP-Final Inspection8/29/20078/30/20078/30/2007 5:54:09 PMACANC
Overbooked
BLD07-00913 FIRE-Final Inspection8/29/20078/30/20078/30/2007 5:53:24 PMACANC
Overbooked
FIR07-00539 INSP-Alarm Testing8/29/20078/30/20078/30/2007 5:52:34 PMACANC
Overbooked
FIR07-00642 INSP-Sprinkler Rough-in8/29/20078/30/20078/30/2007 5:51:34 PMACANC
Overbooked
FIR07-00441 INSP-Final Inspection8/29/20078/30/20078/30/2007 5:50:44 PMAFAIL
See approved plans sheet FA1 for defficiencies at the south office area inspected today including several blocked horn/strobe notification devices at the open office 105 due to 80" high cubicle partitions, SD at the nac panels in the BCS room is too close to an air return grill, one blocked h/s at the file room due to cabinetry, one overspaced h/s at the west side of office 105, noted the ECS room is not staffed at this time and missing some required items per NFPA 72 ch. 8.
BLD07-00057 FIRE-Final Inspection8/30/20078/30/20078/30/2007 2:53:05 PMPPASS
Fire life safety inspection completed acceptable at structural final per T. Arcoraci.
BLD07-02309 FIRE-Final Inspection8/24/20078/30/20078/30/2007 2:50:24 PMAPASS
Life safety inspection passed.
BLD07-00804 FIRE-Final Inspection8/30/20078/30/20078/30/2007 12:39:38 PMPFAIL
Provide building address numbers, post max. occupant load sign per review notes, post 2A10BC fire extinguishers as discussed and per plan, need to remove the portion of the prep table and storage shelf which extends under the west type 1 hood, one EM light repaired while on site.
FIR07-00712 INSP-Final Inspection8/29/20078/30/20078/30/2007 12:35:19 PMAPASS
The hood suppression system functioned correctly under test conditions, noted prep table with storage shelf that extends under the hood to be removed or cut back from this location- to be verified at BLD final, also need to tag the K class PFE.
BLD07-01014 FIRE-Conference8/30/20078/30/20078/30/2007 11:46:12 AMAFAIL
NOTE: Issued a "DO NOT OCCUPY" order due to occupancy prior to project fire sprinkler and building life safety final approval and acceptance. Noted several items lacking and work not complete-construction in process. Discovered business underway and public occupancy at the time of a requested project related sprinkler rough-in inspection. Notified the contractor, club manager, and S. Rogers of the action taken. No occupancy allowed until related permit work is complete and finaled.
FIR07-00681 INSP-Sprinkler Rough-in8/29/20078/30/20078/30/2007 11:38:02 AMPCANC
Inspection canceled per phone call from contractor, Jeremy at ###-####.
FIR07-00554 INSP-Sprinkler Rough-in8/29/20078/30/20078/30/2007 11:22:27 AMAPART
OH rough in for the second portion of the TI remodel is okay for cover, noted missing ceiling tile and escutcheons at several locations, corrections for the cardio area are complete. Also issued a "Do Not Occupy" order due to occupancy prior to final project completion and acceptance.
FIR07-00620 INSP-Sprinkler Rough-in8/29/20078/30/20078/30/2007 11:17:02 AMAPART
Required corrections noted at the previous inspection have been repaired, OH fire sprinkler modifications for phase one as noted on approved plans are okay for ceiling cover.
FIR07-00708 INSP-Sprinkler Rough-in8/30/20078/30/20078/30/2007 10:17:14 AMPPART
OH rough-in is approved for cover at the drop ceilings.
FIR07-00709 INSP-Final Inspection8/29/20078/30/20078/30/2007 10:15:15 AMANR
Permit final pending field ceiling tile and escutcheons.
FIR07-00709 INSP-Sprinkler Rough-in8/29/20078/30/20078/30/2007 10:12:20 AMAPART
OH fire sprinkler modifications are acceptable.
FIR07-00026 FIR-Aging Inspection8/30/20078/30/20078/30/2007 10:10:09 AM DEFR
Work in progress
BLD07-01644 FIRE-Final Inspection8/28/20078/30/20078/30/2007 12:00:00 AMPCANC
carrie - fire life safety Phone #: ###-####