Inspections for the day of: Monday, August 30, 2010.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00282 INSP-Final Inspection8/30/20108/30/20108/31/2010 11:28:43 AMAPASS
Fire sprinkler permit work passed final walkthrough. Permit finaled.
BLD10-01337 FIRE-Final Inspection8/27/20108/30/20108/30/2010 4:23:22 PMAPASS
Correction items verified for completion. Fire life safety finaled.
BLD10-01336 FIRE-Final Inspection8/27/20108/30/20108/30/2010 4:23:03 PMAPASS
Correction items verified for completion. Fire life safety finaled.
FIR10-00418 INSP-Final Inspection8/28/20108/30/20108/30/2010 4:21:54 PMPPASS
Fire alarm work passed field testing. Permit finaled.
FIR10-00417 INSP-Final Inspection8/30/20108/30/20108/30/2010 4:21:36 PMPPASS
Fire alarm work passed field testing. Permit finaled.
FIR09-00080 INSP-Final Inspection8/27/20108/30/20108/30/2010 4:20:13 PMPPART
Fire alarm testing completed satisfactory with the exception of the main control valve tamper switch at the sprinkler riser. Permit final pending repair.
FIR10-00282 INSP-Final Inspection8/30/20108/30/20108/30/2010 4:16:13 PMPPART
Fire sprinkler permit finaled.
BLD10-00336 FIRE-Final Inspection8/27/20108/30/20108/30/2010 1:14:41 PMAPASS
Fire life safety passed. One exit sign at the back office area hall door to be removed, discussed 3 hr fire door with the manager on site.