Inspections for the day of: Monday, August 30, 2010.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00390 INSP-Sprinkler Rough-in/Hydro8/30/20108/30/20108/30/2010 3:48:32 PMPFAIL
More than a single head has been supplied from a single drop and the existing upright sprinkles are overspaced off of the new full height wall.
FIR09-00083 INSP-Final Inspection8/27/20108/30/20108/30/2010 3:16:16 PMPCANC
Per the fire alarm tech a intella tap was installed that was not reflected on the city approved plans as is required. No inspection was performed.
FIR10-00336 INSP-Final Inspection8/27/20108/30/20108/30/2010 3:14:44 PMAFAIL
Provide one additional smoke detector in the ceiling pocket outside of the conference room. Also the EOL did not meet the minimum 19.6 volts. It appears that the notification circuit wil need to be split. This modification will require a resubmittal. Also the horns did not sync.
FIR09-00012 INSP-Final Inspection8/27/20108/30/20108/30/2010 2:50:22 PMPFAIL
The netcon passed but the inspection was stopped since a intella tap was being utilized that is not reflected on the city approved plans.
BLD10-01537 FIRE-Final Inspection8/27/20108/30/20108/30/2010 2:07:28 PMAFAIL
THe building address is incorrect and the fire extinguishers need installed as discussed
BLD10-01391 FIRE-Final Inspection8/27/20108/30/20108/30/2010 10:01:38 AMAFAIL
Provide building address, mount fire extinguisher, provide automatic flush bolts for the inactive leaf of the double doors from the BreakRoom, remove the keyed hardware from one of the two main exit doors and provide with single action hardware. The door that is to remain keyed needs the sticker provided as discussed.
BLD10-01605 FIRE-Final Inspection8/27/20108/30/20108/30/2010 9:59:31 AMAPASS
Life safety passed
FIR09-00083 INSP-Alarm Testing8/27/20108/30/20108/27/2010 3:02:03 PMPCANC
Please call Bill at ###-#### with inspection time Phone #: ###-#### >> Inspection requested via web by Lori Brungardt Inspection cancelled from web by: Lori Brungardt