ELE11-01053
| ELE-Aging Inspection | 8/30/2012 | 8/30/2012 | 8/30/2012 2:51:19 PM | | DONE |
|
|
still under construction
|
ELE12-01628
| Final | 8/30/2012 | 8/30/2012 | 8/30/2012 2:50:19 PM | P | CANC |
|
|
dean Phone #: ###-#### unable to perform inspection
|
ELE12-02179
| Permanent Service | 8/30/2012 | 8/30/2012 | 8/30/2012 2:00:44 PM | P | FAIL |
|
|
Robert Phone #: ###-#### called, no work space about equipment, dead-front not legal, shall check trailer wire and breaker size, shall fix front access door hinge
|
ELE11-02855
| Electrical Rough-In | 8/30/2012 | 8/30/2012 | 8/30/2012 1:14:27 PM | P | PASS |
|
|
Steve Phone #: ###-#### 2 columns only anop ok cover, rest covered, they will open and get inspection since too many bends and not strapped after opening 1
|
ELE12-02178
| Electrical Rough-In | 8/30/2012 | 8/30/2012 | 8/30/2012 12:22:08 PM | P | PASS |
|
|
Key is under rock on front porch Phone #: ###-#### >> Inspection requested via web by Eric Brown ri ok
|
ELE12-01500
| Final | 8/29/2012 | 8/30/2012 | 8/30/2012 11:37:29 AM | A | FAIL |
|
|
>> Inspection requested via web by Stephanie White called, shall provide listing and disconnect for pylon sign
|
ELE12-00971
| Final | 8/29/2012 | 8/30/2012 | 8/30/2012 11:05:34 AM | A | PART |
|
|
call Art with questions Phone #: ###-#### >> Inspection requested via web by Lee VanSchoiack signed t/o card, shall install cord caps and receptacles for ceiling lighting, show window receptacles, drinking fountain gfci, repair hall receptacle per code, add gfci for counter
|
ELE12-01920
| Electrical Rough-In | 8/29/2012 | 8/30/2012 | 8/30/2012 10:18:17 AM | A | PASS |
|
|
Please provide a rough-in inspection. Call Ron ###-####. Have a wonderful day!! Phone #: ###-#### >> Inspection requested via web by Kevin Perez walls ok
|
ELE12-01920
| Permanent Service | 8/30/2012 | 8/30/2012 | 8/30/2012 10:15:01 AM | A | PASS |
|
|
Please provide a rough-in inspection. Call Ron ###-####. Have a wonderful day!! Phone #: ###-#### >> Inspection requested via web by Kevin Perez p/s o/h rec ok
|
ELE12-02169
| Final | 8/29/2012 | 8/30/2012 | 8/30/2012 9:51:48 AM | A | PASS |
|
|
Inspection on wiring for new heat pump, any questions call Jake @ ###-####. Please call homeowner @ ###-#### to meet and be let in. Phone #: ###-#### >> Inspection requested via web by Andy Rose ok final
|
ELE12-02173
| Final | 8/29/2012 | 8/30/2012 | 8/30/2012 9:34:16 AM | A | PASS |
|
|
This is a nuclear pharmacy. We added 2 outlets for tennant use. Please call for entry instructions. Thanks Phone #: ###-#### >> Inspection requested via web by jason shifflett ok final
|
ELE12-01408
| Electrical Rough-In | 8/29/2012 | 8/30/2012 | 8/30/2012 9:05:01 AM | A | PASS |
|
|
Inspection for cover of the walls in the front office. Sean is the on site contact. Thanks. Phone #: ###-#### >> Inspection requested via web by Chad McKibben walls ok, left correction notice to owner and contractor, NEC 725.25 shall remove abandoned lv cable, 300.11 cables and raceways shall not be supported by ceiling grid or tiles
|
ELE12-01742
| Final | 8/30/2012 | 8/30/2012 | 8/30/2012 8:31:03 AM | A | CANC |
|
|
Call Dene with access code Thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser unable to process at this time
|
ELE12-02145
| Temporary Service | 8/29/2012 | 8/30/2012 | 8/30/2012 8:18:06 AM | A | PASS |
|
|
Please contact Cody with any questions ####-#### Phone #: ###-#### >> Inspection requested via web by Tracy Robertson t/s u/g n ok
|
ELE12-02147
| Temporary Service | 8/29/2012 | 8/30/2012 | 8/30/2012 8:16:43 AM | A | PASS |
|
|
Please contact Cody with any questions ####-#### Phone #: ###-#### >> Inspection requested via web by Tracy Robertson t/s u/g n ok
|
ELE12-02166
| Rough-In Permanent Service | 8/29/2012 | 8/30/2012 | 8/30/2012 8:00:53 AM | A | PASS |
|
|
rough and service inspection thank you Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe ri ok, p/s u/g n ok
|