Inspections for the day of: Thursday, August 30, 2012.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00623 FIR-Aging Inspection8/30/20128/30/20129/5/2012 7:00:13 PM DONE
Final scheduled 9/6.
FIR12-00426 INSP-Sprinkler Rough-in8/29/20128/30/20128/31/2012 4:49:04 PMPPART
Okay to cover scope of work indicated on permit documents.
FIR10-00213 FIR-Aging Inspection8/30/20128/30/20128/31/2012 2:23:14 PM DEFR
BLD12-00534 FIRE-Final Inspection8/30/20128/30/20128/31/2012 12:13:01 PMPPASS
Fire life safety passed.
FIR12-00406 INSP-Final Inspection8/30/20128/30/20128/30/2012 4:29:30 PMPPASS
Final walkthrough passed. Permit finaled.
BLD12-00764 FIRE-Final Inspection8/30/20128/30/20128/30/2012 4:08:07 PMPNR
Mike - life safety Phone #: ###-#### * Final pending project related FIR permit for the hood suppression system
BLD12-01809 FIRE-Final Inspection8/30/20128/30/20128/30/2012 4:07:06 PMPPASS
Scope of work completed. Fire life safety inspection passed.
FIR12-00444 INSP-Final Inspection8/29/20128/30/20128/30/2012 3:24:20 PMPCANC
Call prior to going Phone #: 9411846 >> Inspection requested via mobile web by Brian Anderson Inspection cancelled via mobile web on Thursday, August 30, 2012.
FIR11-00543 INSP-Final Inspection8/29/20128/30/20128/30/2012 3:20:34 PMPNR
FIR11-00650 INSP-Final Inspection8/29/20128/30/20128/30/2012 3:19:52 PMAPART
Completed initial walkthrough of the basement, first floor and mechanical mezzanine areas. Items noted include; missing lock and labels at the panel breakers, need to relocate the SD at the FACP, provide signage at the door to the FACP room, relocate MP at the riser, include added FSD at the elevator machine room on record drawings, provide missing occupant notification at the pantry locker/dressing room and the shop RR, replace ceiling mount horn at the chiller, need to verify min. dB is met at the storage rooms, visual coverage at the mens and womens dressing rooms 010 and 012 may be insufficient, provide strobe at the NW womens locker WC, provide coverage or a separation door at closet 109, instruction room 161 cd settings revised while on site, a/v at the brides room relocated to the opposite wall, "storage" room 196 will need occupant notification due to change in room use, need to verify dB measurements at the mechanical mezzanine and listing for concealed a/v's on the first floor.
BLD12-01987 FIRE-Final Inspection8/29/20128/30/20128/30/2012 3:02:10 PMAPASS
C/N item verified for completion. Fire life safety finaled.
BLD12-00814 FIRE-Final Inspection8/29/20128/30/20128/30/2012 3:01:08 PMAPASS
Fire life safety inspection completed satisfactory- missing inspection record on site.
FIR12-00480 INSP-Final Inspection8/28/20128/30/20128/30/2012 2:59:39 PMANR
Missing appliances, installation incomplete.
BLD12-01266 FIRE-Final Inspection8/29/20128/30/20128/30/2012 2:58:32 PMAPASS
Correction items verified for completion. Fire life safety passed- * no signature card available on site.