Inspections for the day of: Friday, August 30, 2013.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD13-00914 FIRE-Final Inspection8/30/20138/30/20138/30/2013 3:45:01 PMPPASS
life safety passed. Fire alarm to be covered under the upgrade agreement.
FIR12-00648 INSP-Final Inspection8/29/20138/30/20138/30/2013 3:10:09 PMACANC
Canceled per voice mail. johnathon Phone #: ###-####
BLD13-01745 FIRE-Final Inspection8/30/20138/30/20138/30/2013 2:40:26 PMPFAIL
Provide one additional emergency light in the corridor as marked on the city approved plans and provide the missing double sided exit sign at this same corridor. Also repair all emergency lighting as marked on the plans and all of the emergency lighting in the existing/to remain area. The photo cells on the exit discharge lights need to be addressed as discussed.
BLD13-00021 FIRE-Final Inspection8/29/20138/30/20138/30/2013 2:38:10 PMAFAIL
Life safety can be passed when the project related fire alarm permit has been finaled.
FIR13-00086 INSP-Final Inspection8/28/20138/30/20138/30/2013 2:37:19 PMAFAIL
Need revised as-builts showing the 110 cd strobes and the deluge system solenoids, the west deluge system flow/pressure switch is reporting as a PIV supervisory and the Low Air pressure switch did not report at all. Waiting on the solenoid switch for the east deluge system as well.
FIR13-00164 INSP-Final Inspection8/30/20138/30/20138/30/2013 1:59:09 PMPPASS
permit finaled
FIR13-00135 INSP-Final Inspection8/30/20138/30/20138/30/2013 1:58:18 PMPPASS
permit finaled
BLD13-02341 FIRE-Final Inspection8/29/20138/30/20138/30/2013 1:05:52 PMAPART
A temporary occupancy was given until a permit is issued/inspected to either remove the fire alarm devices(if applicable) or to extend the fire alarm system into areas in the tenant space not currently served by the fire alarm system. I found a horn/strobe with a pull staion in the Future Dance Studio and two smoke detectors in the Hall
BLD12-01487 FIRE-Final Inspection8/29/20138/30/20138/30/2013 11:17:14 AMAPART
The fire doors in the Lube Bay and the new Service Shop passed inspection. Links are on both sides of the wall and at the deck.
BLD13-00028 FIRE-Final Inspection8/29/20138/30/20138/30/2013 10:04:12 AMAPASS
Life safety passed
FIR13-00384 INSP-Final Inspection8/30/20138/30/20138/30/2013 10:02:31 AMAPASS
Permit finaled
FIR12-00610 INSP-Final Inspection8/29/20138/30/20138/30/2013 9:55:09 AMACANC
Please call Perly 30 minutes prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
BLD13-02341 FIRE-Final Inspection8/29/20138/30/20138/29/2013 4:59:52 PMACANC
Please call 1 hr before Ralph Seal Phone #: ###-#### >> Inspection requested via web by Dennis Harmon Inspection cancelled from web by: Dennis Harmon