BLD13-00914
| FIRE-Final Inspection | 8/30/2013 | 8/30/2013 | 8/30/2013 3:45:01 PM | P | PASS |
|
|
life safety passed. Fire alarm to be covered under the upgrade agreement.
|
FIR12-00648
| INSP-Final Inspection | 8/29/2013 | 8/30/2013 | 8/30/2013 3:10:09 PM | A | CANC |
|
|
Canceled per voice mail. johnathon Phone #: ###-####
|
BLD13-01745
| FIRE-Final Inspection | 8/30/2013 | 8/30/2013 | 8/30/2013 2:40:26 PM | P | FAIL |
|
|
Provide one additional emergency light in the corridor as marked on the city approved plans and provide the missing double sided exit sign at this same corridor. Also repair all emergency lighting as marked on the plans and all of the emergency lighting in the existing/to remain area. The photo cells on the exit discharge lights need to be addressed as discussed.
|
BLD13-00021
| FIRE-Final Inspection | 8/29/2013 | 8/30/2013 | 8/30/2013 2:38:10 PM | A | FAIL |
|
|
Life safety can be passed when the project related fire alarm permit has been finaled.
|
FIR13-00086
| INSP-Final Inspection | 8/28/2013 | 8/30/2013 | 8/30/2013 2:37:19 PM | A | FAIL |
|
|
Need revised as-builts showing the 110 cd strobes and the deluge system solenoids, the west deluge system flow/pressure switch is reporting as a PIV supervisory and the Low Air pressure switch did not report at all. Waiting on the solenoid switch for the east deluge system as well.
|
FIR13-00164
| INSP-Final Inspection | 8/30/2013 | 8/30/2013 | 8/30/2013 1:59:09 PM | P | PASS |
|
|
permit finaled
|
FIR13-00135
| INSP-Final Inspection | 8/30/2013 | 8/30/2013 | 8/30/2013 1:58:18 PM | P | PASS |
|
|
permit finaled
|
BLD13-02341
| FIRE-Final Inspection | 8/29/2013 | 8/30/2013 | 8/30/2013 1:05:52 PM | A | PART |
|
|
A temporary occupancy was given until a permit is issued/inspected to either remove the fire alarm devices(if applicable) or to extend the fire alarm system into areas in the tenant space not currently served by the fire alarm system. I found a horn/strobe with a pull staion in the Future Dance Studio and two smoke detectors in the Hall
|
BLD12-01487
| FIRE-Final Inspection | 8/29/2013 | 8/30/2013 | 8/30/2013 11:17:14 AM | A | PART |
|
|
The fire doors in the Lube Bay and the new Service Shop passed inspection. Links are on both sides of the wall and at the deck.
|
BLD13-00028
| FIRE-Final Inspection | 8/29/2013 | 8/30/2013 | 8/30/2013 10:04:12 AM | A | PASS |
|
|
Life safety passed
|
FIR13-00384
| INSP-Final Inspection | 8/30/2013 | 8/30/2013 | 8/30/2013 10:02:31 AM | A | PASS |
|
|
Permit finaled
|
FIR12-00610
| INSP-Final Inspection | 8/29/2013 | 8/30/2013 | 8/30/2013 9:55:09 AM | A | CANC |
|
|
Please call Perly 30 minutes prior Phone #: ###-#### >> Inspection requested via web by Jacci Hunt Inspection cancelled from web by: Jacci Hunt
|
BLD13-02341
| FIRE-Final Inspection | 8/29/2013 | 8/30/2013 | 8/29/2013 4:59:52 PM | A | CANC |
|
|
Please call 1 hr before Ralph Seal Phone #: ###-#### >> Inspection requested via web by Dennis Harmon Inspection cancelled from web by: Dennis Harmon
|