Inspections for the day of: Wednesday, August 31, 2005.
Number of inspections: 29
Percentage of inspections complete: 97 %
Percentage of inspections not complete: 3 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-01362 FIRE-Final Inspection8/31/20058/31/20059/6/2005 1:45:10 PMPPASS
tom; Phone #: ###-#### This inspection to be completed by Mary Froemke at the same time as the fire alarm inspection scheduled for 9/7/05 pm.

Life safety passed, fire extinguishers in cabinets with current tags, all interior door hardware has levers and exit doors are crash bars. Egress (internal and external) lighting was acceptable and exit signs functional.
FIR05-00552 INSP-Final Inspection8/31/20058/31/20059/1/2005 3:26:19 PMPDEFR
This inspection to be performed by Mary Froemke due to scheduling conflicts.
BLD04-03004 FIRE-Final Inspection8/31/20058/31/20059/1/2005 3:16:10 PMPFAIL
Smoke alarm installation must meet requirements of NFPA 72 2002, see fire code review notes #2 and #3.
BLD04-02991 FIRE-Final Inspection8/31/20058/31/20059/1/2005 3:14:45 PMPFAIL
Smoke alarm installation must meet requirements of NFPA 72 2002, see fire code review notes #2 and #3.
BLD04-03005 FIRE-Final Inspection8/31/20058/31/20059/1/2005 3:13:14 PMPFAIL
Smoke alarm installation must meet requirements of NFPA 72 2002, see fire code review notes #2 and #3.
BLD05-01322 FIRE-Final Inspection8/31/20058/31/20059/1/2005 12:03:35 PMPFAIL
Need to verify door hardware operation at two doors to closets.
MIS05-00132 FIR-Final8/31/20058/31/20059/1/2005 9:01:37 AMPPASS
Fire life safety passed inspection.
FIR05-00453 INSP-Final Inspection8/31/20058/31/20059/1/2005 12:00:00 AMPCANC
Grant's phone. Must be after 4 pm. Thanks; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
BLD05-00127 FIRE-Final Inspection8/31/20058/31/20058/31/2005 3:49:46 PMPPASS
Fire life safety is satisfactory.
BLD05-01718 FIRE-Final Inspection8/31/20058/31/20058/31/2005 3:17:20 PMPPASS
HVAC duct smoke detectors shut down units upon activation, fire life safety finaled.
FIR05-00483 INSP-Final Inspection8/31/20058/31/20058/31/2005 3:01:14 PMPPASS
Fire sprinkler permit finaled, contractor to install globe valves on test header connections in addition to the brass caps due to the close proximity of the remote FDC to eliminate confusion between the two in addition to provided signage.
BLD05-01200 FIRE-Final Inspection8/31/20058/31/20058/31/2005 2:14:00 PMPPASS
Fire life safety passed inspection.
BLD05-01345 FIRE-Final Inspection8/31/20058/31/20058/31/2005 1:12:42 PMPFAIL
Fire alarm must be completed and inspected prior to fire life safety sign off.
BLD04-01823 FIRE-Final Inspection8/31/20058/31/20058/31/2005 1:10:52 PMPCANC
robie; Phone #: ###-#### Contractor is not ready for inspection.
MIS05-00137 FIR-Final8/30/20058/31/20058/31/2005 12:59:18 PMAPASS
Life safety passed inspection.
FIR05-00394 INSP-Final Inspection8/30/20058/31/20058/31/2005 12:58:28 PMAFAIL
The strobe in the confrence room is mounted too low for code requirements, duct smoke detectors tested okay, no other items inspected.
BLD05-01283 FIRE-Final Inspection8/30/20058/31/20058/31/2005 12:56:15 PMAFAIL
Need to install fire extinguishers with current inspection tags, provide permanent suite address.
BLD05-01687 FIRE-Final Inspection8/30/20058/31/20058/31/2005 12:55:06 PMAFAIL
Need to install fire extinguishers as discussed.
FIR05-00437 INSP-Conference8/30/20058/31/20058/31/2005 10:47:20 AMADONE
Duplicate inspection, already completed.
FIR05-00437 INSP-Sprinkler Rough-in8/30/20058/31/20058/31/2005 10:46:05 AMAFAIL
Quick and standard response heads are mixed within the same room, three heads piped off 1" in 3 areas as marked on plans is not allowed unless the required fire separation rating can be met, provide head guards on SW heads below overhead doors.
FIR05-00186 INSP-Final Inspection8/30/20058/31/20058/31/2005 10:36:19 AMAPART
Inspected devices at the dollar store riser, dry cleaners, golf store, knox box, and all relocated pull stations in the west portion of shopping center.
BLD05-02038 FIRE-Final Inspection8/30/20058/31/20058/31/2005 10:31:44 AMAPASS
Fire life safety passed inspection, contractor to call with verification of a current annual inspection on the fire sprinkler system which serves this space.
FIR05-00372 INSP-Sprinkler Rough-in8/30/20058/31/20058/31/2005 10:23:37 AMAFAIL
Two heads in 2nd floor restroom hard lid are spaced 5' apart, missing retaining strap on hanger in hallway, incorrect head spacing at soffit as marked on approved plans, inspection was for sheet FP 5 second floor.
FIR05-00273 INSP-Sprinkler Rough-in/Hydro8/30/20058/31/20058/31/2005 12:00:00 AMPPART
3rd floor (4 dormers) addition and full hydro test.
rick; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
FIR05-00044 INSP-Final Inspection8/30/20058/31/20058/31/2005 12:00:00 AMPPART
Forrest, Here is the inspection request for the completion of the final test at Trinity Presbyterian. If there is any problems meeting out there at 12:00p.m., please let us know. My cell is ###-#### if you cannot reach me at the office. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick

Forrest, all checked out, one final issue is the phone lines are routed to the General Contractors trailer (temproary), so I did not test them. ESI is aware of the situation and will need to determine their plan of attack. I have told Jason and he will contact them. They have a choice of two options. 1) Provide the two permanent phone lines and test. 2) If they want to request a "temp" so they can move this weekend, they will need to supply a letter stating the trailer and phone lines will remain intact til the permanent ones are provided, probably need to test also. Sam is off tomorrow, so if they want a temp, they will need to request it today.
FIR05-00373 INSP-Final Inspection8/30/20058/31/20058/31/2005 12:00:00 AMPCANC
Jonathan is the contact on this job. Thank you; Phone #: ###-#### Internet Inspection Request from: Trent Bice
Contractor not available at site.
FIR05-00551 INSP-Final Inspection8/31/20058/31/20058/31/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 8/31/2005 at 10:44:45 AM. Contact: ###-####.
FIR05-00342 INSP-Final Inspection8/31/20058/31/20058/31/2005 12:00:00 AMPPASS
Fire sprinkler permit finaled.
FIR05-00209 INSP-Final Inspection8/30/20058/31/2005 A 
Scheduled by a contractor via Hello! on 8/30/2005 at 4:20:18 PM. Contact: ###-####.