PLM06-02964
| Groundwork | 8/31/2006 | 8/31/2006 | 8/31/2006 4:47:41 PM | P | PASS |
|
|
Randy; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
|
PLM06-02764
| Plumbing Rough-in | 8/30/2006 | 8/31/2006 | 8/31/2006 4:13:37 PM | P | PASS |
|
|
|
PLM05-03314
| Final | 8/30/2006 | 8/31/2006 | 8/31/2006 4:03:00 PM | A | PART |
|
|
made walk through with Donny has some miscellaneous item,s to finish and caulk floor sink in nourish room ( room # 16417 ) where dishwasher is to be installed may have to be moved for access for repairs and cleaning will discuss with Lee Rice chief plumbing inspector . owner supplied ice machine,s may require additional backflow protection
|
PLM05-04309
| Med/Gas Systems | 8/30/2006 | 8/31/2006 | 8/31/2006 12:37:58 PM | A | PART |
|
|
24 hr pressure test on second floor med gas main trunk lines up to wall zone valves test ok still need to test down stream of zone valves still need some additional labeling of piping and valves
|
PLM06-02019
| Final | 8/30/2006 | 8/31/2006 | 8/31/2006 9:43:57 AM | A | PART |
|
|
Call Doran please; Phone #: ###-#### Internet Inspection Request from: joe paige need to lite off water heater and adjust lav faucets for 120 degree hot water limitation need to install an RP for water supply to swamp cooler called contractor will recall when ready
|
PLM06-01117
| Water and/or Sewer | 8/30/2006 | 8/31/2006 | 8/31/2006 8:45:48 AM | A | CANC |
|
|
This is for a final inspection please call if you have any questions or concerns; Phone #: ###-#### Internet Inspection Request from: Kirk Johns
|
PLM06-01117
| Final | 8/31/2006 | 8/31/2006 | 8/31/2006 8:45:27 AM | A | PASS |
|
|
unable to sign off card general contractor not on site and construction trailer locked up
|
PLM06-02939
| Groundwork | 8/30/2006 | 8/31/2006 | 8/31/2006 8:26:21 AM | A | PASS |
|
|
Call Doran please; Phone #: ###-#### Internet Inspection Request from: joe paige
|