Inspections for the day of: Thursday, August 31, 2006.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00750 FIR-Aging Inspection8/31/20068/31/20069/5/2006 2:45:30 PM DONE
wip
FIR05-00425 INSP-Sprinkler Rough-in/Hydro8/31/20068/31/20069/1/2006 9:09:40 AMPPART
Drop ceiling areas in the confrence rooms, adjacent to the pool, and SE of stairs are okay to cover. Noted two overspaced heads in in the public restrooms.
FIR06-00539 INSP-Final Inspection8/29/20068/31/20068/31/2006 3:24:44 PMPCANC
rob's phone Internet Inspection Request from: Terry Owsley Cancel per contractor
FIR06-00538 INSP-Final Inspection8/29/20068/31/20068/31/2006 3:24:21 PMPCANC
rob's phone Internet Inspection Request from: Terry Owsley Cancel per contractor
FIR06-00405 INSP-Final Inspection8/30/20068/31/20068/31/2006 2:59:08 PMPPASS
Fire alarm passed final inspection.
BLD06-01416 FIRE-Final Inspection8/31/20068/31/20068/31/2006 2:22:40 PMPPASS
Items on previous c/n have been verified for completion, inspeciton passed.
FIR06-00533 INSP-Final Inspection8/30/20068/31/20068/31/2006 2:21:17 PMAPASS
Corrections are complete, permit finaled.
FIR06-00133 INSP-Final Inspection8/30/20068/31/20068/31/2006 2:11:49 PMAPASS
Fire alarm work passed field inspection, noted plan modification to delete duct detectors as the individual units are below 2000 cfm and do not share common ducting or plenum.
FIR06-00556 INSP-Sprinkler Rough-in8/29/20068/31/20068/31/2006 12:27:28 PMAPART
OH sprinkler rough-in is good for cover at the hard lid areas.
FIR06-00588 INSP-Sprinkler Rough-in8/30/20068/31/20068/31/2006 11:24:24 AMAPART
OH rough-in is good for cover at the west portion of phase 2 remodel as marked on approved plans.
BLD05-02973 FIRE-Final Inspection8/30/20068/31/20068/31/2006 11:23:09 AMAPASS
Life safety inspection passed.
FIR06-00377 INSP-Final Inspection8/30/20068/31/20068/31/2006 10:28:56 AMAPASS
Fire sprinkler permit finaled.
FIR06-00410 INSP-Final Inspection8/30/20068/31/20068/31/2006 10:28:19 AMAFAIL
Fire rated doors are not properly adjusted for complete closure at the new pass through, notification devices not coordinated for testing at this time.
FIR06-00537 INSP-Final Inspection8/29/20068/31/20068/29/2006 5:08:07 PMPCANC
rob's phone Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley